Parameter
Program
P53
1
P54
2
P55
OFF
P61
OFF
PLUS
APPENDIX
9
9.2 - RECOMMENDED APPLICATION WITH TERMINALS FOR TWO
WIRE CONTROL
Obs.:
It's necessary to use normal fuses or breaker to protect
the installation. Ultra-Fast fuses are not necessary for
the SSW-03 Plus operation, but they are recommended
for SCR protection.
The transformer "T" is optional and must be utilized
when the line voltage is different than the electronics
and fan voltage.
For the integral motor protection it's recommended to
install one or more thermostats in the motor. If the ther-
mostat is not used, the external input error (DI3) from
SSW-03 Plus must be connected to +Vdc.
NOTE!
A contactor in the mains input (see 9.4) is necessary to pro-
tect the motor in case there is a phase failure which is caused
by damage in the SSW-03 Plus power circuit with the appli-
cation of the power isolation contactor.