Quick Reference of Parameters
SRW 01 | 0-7
0
Parameter
Description
Adjustable Range
Factory
Setting
User
Setting
Proprieties Page
P606
External Fault Protection
0 = Disabled
1 = Enabled
0
Sys, rw
P607
Auto-reset External Fault
0 = Disabled
1 = Enabled
0
Sys, rw
P608
External Fault Timing
0 = Disabled
1 = Enabled
0
Sys, rw
P609
External Fault Time
1 to 99 s
1 s
Sys, rw
P610
External Fault Monitoring of
Protection
0 = Always
1 = Only When the Motor is Running
0
Sys, rw
P611
External Fault Signal
0 = Digital Input I11
1 = Digital Input I12
2 = Digital Input I13
3 = Digital Input I14
4 = Digital Input I15
5 = Digital Input I16
3
Sys, rw
P612
External Fault Signal Logic
0 = Digital Input NC
1 = Digital Input NO
1
Sys, rw
P613
External Fault Protection Action
0 = Alarm
1 = Switch Off (Trip)
1
Sys, rw
P614
Current Imbalance
5 to 100 %
40 %
Sys, rw
P615
Current Imbalance Time
0 = Disabled
1 to 99 s = Enabled
3 s
Sys, rw
P616
Current Imbalance Protection Action 0 = Alarm
1 = Switch Off (Trip)
1
Sys, rw
P617
Earth Fault
40 to 100 %
50 %
Sys, rw
P618
Earth Fault Time
0 = Disabled
1 to 99 s = Enabled
3 s
Sys, rw
P619
Earth Fault Protection Action
0 = Alarm
1 = Switch Off (Trip)
1
Sys, rw
P620
Phase Loss (Current) Time
0 = Disabled
1 to 99 s = Enabled
3 s
Sys, rw
P621
Phase Loss (Current) Protection
Action
0 = Alarm
1 = Switch Off (Trip)
1
Sys, rw
P622
Overcurrent
50 to 1000 %
400 %
Sys, rw
P623
Overcurrent Time
0 = Disabled
1 to 99 s = Enabled
3 s
Sys, rw
P624
Overcurrent Protection Action
0 = Alarm
1 = Switch Off (Trip)
1
Sys, rw
P625
Undercurrent
5 to 100 %
20 %
Sys, rw
P626
Undercurrent Time
0 = Disabled
1 to 99 s = Enabled
0 s
Sys, rw
P627
Undercurrent Protection Action
0 = Alarm
1 = Switch Off (Trip)
1
Sys, rw
P628
Frequency Out of Range
5 to 20 %
5 %
Sys, rw
P629
Frequency Out of Range Time
0 = Disabled
1 to 99 s = Enabled
0 s
Sys, rw
P630
Frequency Out of Range Protection
Action
0 = Alarm
1 = Switch Off (Trip)
1
Sys, rw
P631
Earth Leakage Protection
0 = Disabled
1 = Enabled
0
Sys, rw
P632
Earth Leakage Current Level
Selection
0 = 0.3 A
1 = 0.5 A
2 = 1 A
3 = 2 A
4 = 3 A
5 = 5 A
2
Sys, rw
P633
Earth Leakage Time
0.1 to 99.0 s
0.5 s
Sys, rw
P634
Earth Leakage Protection Action
0 = Alarm
1 = Switch Off (Trip)
1
Sys, rw
P635
Earth Leakage Start Up Inhibit
0 = Disabled
1 = Enabled
0
Sys, rw