Parameterization
SRW 01 | 5-59
5
Table 5.16:
Function stage of test Trip
Normal Operation: Leds and Output
Motor Off
Motor On
First stage: Reset Button pressed between 1 s - 3 s
Led net
Signaling as per
Red/green flash
Red/green flash
Led status
Green
Red
Red
Led Trip
Green
Red
Red
Output(s)
Unchanged
Unchanged
Unchanged
Second Stage: Reset Button Pressed Between 3 s - 5 s
Led net
Signaling as per
Led status
Green
Green
Green
Led Trip
Green
Red flashlight
Red intermittent flash
Output(s)
Unchanged
Unchanged
Unchanged
Third Stage: Reset Button Pressed > 5 s
Led net
Signaling as per
Led status
Green
Red flashlight
Red flashlight
Led Trip
Green
Red flashlight
Red flashlight
Output(s)
Changed, switch Off (Trip)
Changed, switch Off (Trip)
Changed, switch Off (Trip)
If the reset button placed on the front part of the Control Unit remains pressed between1 to 3 s, the verification
of the Net, Trip and status leds is made. If during this stage the HMI is connected to the Control Unit, it will show
on the display
and change the state of the leds near the keys
which indicate the direction
of the rotation/speed of the motor and
, which indicate the operation mode of the SRW 01 Local/Remote.
If the button remains pressed from 3 to 5 s, the Trip led will send out a signal that it will enter the next stage of the
test simulating a Trip state if the time surpasses 5 s and opening the output(s) that drive(s) the motor (according to
operation Mode - P202), signaling error on the status led and the message “E0087” on the HMI.
NOTE!
Check the correct operation of the net, Trip and status leds, display of the HMI and contactor of the
digital output(s) periodically.
NOTE!
The Trip Test function can be disabled using parameter P602. Activation when the motor is operating
will disconnect it if the third stage of the test is started.
P602 – Function Test/Reset Button
Adjustable
Range:
0 = Disabled
1 = Enabled
Factory
Setting:
1
Proprieties:
Sys, rw
Description:
It ables or disables the trip test function through the reset button placed on the front of the control unit.
5.7.26 Reset to the Factory Settings
In order to load the SRW 01 factory settings, the next procedure must be followed:
1. Remove the power supply from the SRW 01.