Parameterization
SRW 01 | 5-3
5
Description:
It defines the origin of the Local commands.
If the remote mode is selected, the origin of the Remote commands must be defined at the parameter P232.
P315 – Action in the Local/Remote Transition
Adjustable
Range:
0 = Keep Motor Status
1 = The Motor is Turned Off
Factory
Setting:
0
Proprieties:
Sys, CFG
Description:
In the transition from Local to Remote control, or vice-versa, it is possible to configure the Control Unit (UC) so
that, according to the selected operation mode (P202), it disables the digital outputs(s), stopping the motor.
NOTE!
The stop motor command will only be executed if current is flowing through the motor (bit 3 of
parameter P006 = 1).
P232 – Remote Command Selection
Adjustable
Range:
0 = Ix
1 = HMI
2 = USB/Ladder
3 = Fieldbus
Factory
Setting:
3
Proprieties:
Sys, rw
Description:
It defines the origin of the Remote commands.
If P229 or P232 = 0, then the Local/Remote commands (start, stop, reversion etc) are controlled by the I11 to
I16 digital inputs, according to the operation mode selected in P202.
If P229 or P232 = 1, then the Local/Remote commands (start, stop, reversion etc) are controlled by the HMI
,
and
keys.
If P229 or P232 = 2 USB/Ladder, then the Local/Remote commands (start, stop, reversion etc) are sent by the
monitoring dialog “control/signals” through the commands LC1, LC2 and LC3, via USB, or by the Ladder user
program, through the system bit markers SX3001 … SX3003 (refer to the WLP manual).
If P232 = 3, the Remote commands are controlled by the industrial network master (refer to the SRW 01
communication manuals).
P233 – Retentive or Impulsive Control (Fieldbus)
Adjustable
Range:
0 = Retentive (Switch)
1 = Impulsive (Pushbutton)
Factory
Setting:
1
Proprieties:
Sys, CFG
Description:
If set P232 = 3, defining that the remote controls are controlled by the master of the industrial network (refer to
the communication network manual), the control type can be selected as:
Retentive (behavior similar to a switch).
Impulsive (behavior similar to pushbutton).