HMI
4-4 | SRW 01
4
The procedure to change the password is described next:
1 – Set the parameter P200 = 2.
2 – The parameter P000 is accessed automatically.
3 – Set the new password value using the increase
and decrease
keys.
4 – Once the new password value has been adjusted, press the
key again.
5 – The parameter P200 is then adjusted automatically to 1 (active password).
P000 – Access to the Parameters
Adjustable
Range:
0 to 999
Factory
Setting:
0
Proprieties:
rw
Description:
It releases, by means of a password, the access for changing the content of the parameters.
P200 – Password Status
Adjustable
Range:
0 = Inactive
1 = Active
2 = Change Password
Factory
Setting:
1
Propriedades:
Sys, rw
Description:
It allows changing the value of the password and/or set its status, configuring it as active or inactive.
NOTE!
In order to disable the password, set the parameter P000 = 5 and the parameter P200 = 0.
4.6 COPY FUNCTION
In order to perform the copy function, it is necessary to use the HMI.
The SRW 01 copy function allows the recording of up to 3 parameter sets and/or 3 user programs.
It presents two procedures:
1. Upload dos dados: SRW 01 para a HMI.
2. Data download: HMI to another SRW 01.
After storing the parameters of the SRW 01 on the HMI it is possible to repass them to another relay using this
function (P500). However, the relays must have the same hardware and the same firmware version. Refer to the
identification label to verify the version of the product.
It is understood that “different hardware” is the model of the control unit with PTC protection (SRW01-PTC), earth
leakage (SRW01-RCD) or Ethernet versions (SRW01-ETH) and that “different version” are those that are different
in “x” or “y” supposing that the number of the firmware versions are described as Vx.yz.
When downloading the parameters (P500), if there is a conflict between the different hardware and/or firmware
versions, the control unit will signal fault on the status led and a “E0010” message on the HMI. Hardware and/or
firmware differences are also verified when downloading the user program (P501).