Quick Reference of Parameters
0-6 | SRW 01
0
Parameter
Description
Adjustable Range
Factory
Setting
User
Setting
Proprieties Page
P295
Currente and/or Voltage
Measurement Unit (UMC/UMCT)
0 = UMC0/UMCT0 (0.25 – 2.5 A)
1 = UMC1/UMCT1 (0.5 – 5 A)
2 = UMC2/UMCT2 (1.25 – 12.5 A)
3 = UMC3/UMCT3 (2.5 – 25 A)
4 = UMC4/UMCT4 (12.5 – 125 A)
5 = UMC5/UMCT5 (42 – 420 A)
6 = UMC6/UMCT6 (84 – 840 A)
7 = UMC1/UMCT1 + External CT
1
Sys, CFG
P296
Number of Turns Through the UMC/
UMCT
1 to 10
1
Sys, CFG
P297
Motor Type
0 = Three-Phase
1 = Single-Phase
0
Sys, CFG
P298
External CT Primary Current
1 a 5000 A
1 A
Sys, CFG
P299
External CT Secondary Current
0 = 1 A
1 = 5 A
0
Sys, CFG
P310
Configuration of the Serial Interface
Bytes
0 = 8 data bits, no parity, 1 stop bit
1 = 8 data bits, even parity, 1 stop bit
2 = 8 data bits, odd parity, 1 stop bit
3 = 8 data bits, no parity, 2 stop bit
4 = 8 data bits, even parity, 2 stop bit
5 = 8 data bits, odd parity, 2 stop bit
3
Sys, CFG
P311
Action for HMI Communication Error 0 = Only Fault Indication
1 = The Motor is Turned Off
0
Sys, rw
P312
Action for EDU Communication
Error
0 = Only Fault Indication
1 = The Motor is Turned Off
0
Sys, rw
P313
Action in Case of Communication
Error
0 = Only Fault Indication
1 = The Motor is Turned Off
2 = The Motor is Turned Off and the
Commands are Reset
3 = It Changes to Local
0
Sys, rw
P315
Action in the Local/Remote
Transition
0 = Keep Motor Status
1 = The Motor is Turned Off
0
Sys, CFG
P400
Motor Nominal Voltage
0 to 1000 V
380 V
Sys, CFG
P401
Motor Nominal Current 1
0.0 to 5000.0 A
0.5 A
Sys, CFG
P402
Motor Nominal Current 2
0.0 to 5000.0 A
0.5 A
Sys, CFG
P404
Motor Rated Power
0.1 to 6553.5 kW
75.0 kW
Sys, CFG
P406
Service Factor
1.00 to 1.50
1.15
Sys, CFG
P407
Line Frequency
0 to 99 Hz
60 Hz
Sys, CFG
P408
Motor Phase Sequence
0 = 1-2-3
1 = 3-2-1
0
Sys, CFG
P500
Parameter Upload/Download
0 = No Function
1 = Save Bank 1
2 = Save Bank 2
3 = Save Bank 3
4 = Load Bank 1
5 = Load Bank 2
6 = Load Bank 3
0
Sys, rw
P501
User Program Upload/Download
0 = No Function
1 = Save Applicative 1
2 = Save Applicative 2
3 = Save Applicative 3
4 = Load Applicative 1
5 = Load Applicative 2
6 = Load Applicative 3
0
Sys, rw
P601
Reset Selection
0 = Without Local Reset
1 = Front Button
2 = Reset key (HMI)
3 = Digital Input I13
4 = Digital Input I14
5 = Digital Input I15
6 = Digital Input I16
1
Sys, rw
P602
Function Test/Reset Button
0 = Disabled
1 = Enabled
1
Sys, rw
P605
Hysteresis
0 to 15 %
5 %
Sys, rw