Quick Reference of Parameters
SRW 01 | 0-5
0
Parameter
Description
Adjustable Range
Factory
Setting
User
Setting
Proprieties Page
P220
Local/Remote Selection
0 = Always Local
1 = Always Remote
2 = HMI key (LOC)
3 = HMI key (REM)
4 = Digital Input I13
5 = Digital Input I14
6 = Fieldbus (LOC)
7 = Fieldbus (REM)
8 = USB/Ladder
9 = Digital Input I15
10 = Digital Input I16
2
Sys, rw
P229
Local Command Selection
0 = Ix
1 = HMI
2 = USB/Ladder
0
Sys, rw
P230
Two or Three-wire Command (Ix)
0 = Two wires (Switch)
1 = Three wires (Pushbutton)
1
Sys, CFG
P231
Stop Logic with Three-wire
Command (Ix)
0 = Digital Input I11 (NC)
1 = Digital Input I11 (NO)
0
Sys, CFG
P232
Remote Command Selection
0 = Ix
1 = HMI
2 = USB/Ladder
3 = Fieldbus
3
Sys, rw
P233
Retentive or Impulsive Control
(Fieldbus)
0 = Retentive (Switch)
1 = Impulsive (Pushbutton)
1
Sys, CFG
P277
Digital Output O1 Function
0 = Internal Use
1 = Ladder
2 = Fieldbus
3 = Alarm/Fault Signal (NO)
4 = Trip/Error Signal (NO)
5 = Trip/Error Signal (NC)
6 = Check Back Signal (NO)
7 = Trip Signal PTC (NO)
8 = Trip Signal Out of Frequency (NO)
9 = Trip Signal Undercurrent (NO)
10 = Trip Signal Overcurrent (NO)
11 = Trip Signal Phase Loss (current) (NO)
12 = Trip Signal Current Imbalance (NO)
13 = Trip Signal Earth Fault (NO)
14 = Trip Signal Overload (NO)
15 = Trip Signal Earth Leakage (NO)
16 = Trip Signal External Fault (NO)
17 = Trip Signal Trip Test (NO)
18 = Trip Signal Phase Sequence (NO)
19 = Trip Signal Voltage Unbalance (NO)
20 = Trip Signal Phase Loss (voltage) (NO)
21 = Trip Signal Overvoltage (NO)
22 = Trip Signal Undervoltage (NO)
23 = Trip Signal Underpower (NO)
24 = Trip Signal Overpower (NO)
25 = Trip Signal Power Under Factor (NO)
26 = Trip Signal Power Over Factor (NO)
0
Sys, CFG
P278
Digital Output O2 Function
See Options in P277
0
Sys, CFG
P279
Digital Output O3 Function
See Options in P277
1
Sys, CFG
P280
Digital Output O4 Function
See Options in P277
1
Sys, CFG
P281
Digital Output O5 Function
See Options in P277
1
Sys, CFG
P282
Digital Output O6 Function
See Options in P277
1
Sys, CFG
P283
Digital Output O7 Function
See Options in P277
1
Sys, CFG
P284
Digital Output O8 Function
See Options in P277
1
Sys, CFG
P294
Expansion Digital Unit (EDU)
0 = EDU Not Used
1 = EDU Used
0
Sys, CFG