0
Quick Reference of Parameters, Alarms and Faults
0-2 | CFW300
Param.
Description
Adjustable Range
Factory Setting
Prop.
Page
P029
Power HW Configuration
0 = Non-identified
1 = 1.6 A / 110 V
2 = 2.6 A / 110 V
3 = 4.0 A / 110 V
4 = 6.0 A / 110 V
5 = 1.6 A / 220 V
6 = 2.6 A / 220 V
7 = 4.0 A / 220 V
8 = 6.0 A / 220 V
9 = 7.3 A / 220 V
10 = 10 A / 220 V
11 = 15.2 A / 220 V
According the
inverter model
ro
P030
Module Temperature
0.0 to 200.0 ºC (32 °F to 392 °F)
ro
P037
Motor Overload Ixt
0.0 to 100.0 %
ro
P038
Encoder Speed
-9999 to 9999 rpm
ro
P039
Encoder Pulse Counter
0 to 9999
ro
P045
Enabled Fan Time
0 to FFFF (hexa)
ro
P047
CONFIG Status
0 to 999
ro
P048
Present Alarm
0 to 999
ro
P049
Present Fault
0 to 999
ro
P050
Last Fault
0 to 999
ro
P051
Last Fault Current
0.0 to 40.0 A
ro
P052
Last Fault DC Link
0 to 524 V
ro
P053
Last Fault Frequency
0.0 to 400.0 Hz
ro
P054
Last Fault Temperature
0.0 to 200.0 ºC (32 °F to 392 °F)
ro
P060
Second Fault
0 to 999
ro
P070
Third Fault
0 to 999
ro
P080
Last Fault in “Fire Mode”
0 to 999 0
ro
P081
Second Fault in “Fire Mode”
0 to 999 0
ro
P082
Third Fault in “Fire Mode”
0 to 999 0
ro
P100
Acceleration Time
0.1 to 999.9 s
5.0 s
P101
Deceleration Time
0.1 to 999.9 s
10.0 s
P102
Acceleration Time 2
nd
Ramp
0.1 to 999.9 s
5.0 s
P103
Deceleration Time 2
nd
Ramp
0.1 to 999.9 s
10.0 s
P104
S Ramp
0 = Inactive
1 = Active
0
cfg
P105
Selection 1
st
/2
nd
Ramp
0 = 1
st
Ramp
1 = 2
nd
Ramp
2 = DIx
3 = Serial/USB
4 = Reserved
5 = CO/DN/DP
6 = SoftPLC
0
P106
Emer. R. Acceleration Time
0.1 to 999.9 s
5.0 s
P107
Emer. R. Time Deceleration
0.1 to 999.9 s
5.0 s
P120
Speed Ref. Backup
0 = Inactive
1 = Active
2 = Backup by P121
1
P121
Reference via HMI
0.0 to 400.0 Hz
3.0 Hz
P122
JOG Reference
-400.0 to 400.0 Hz
5.0 Hz
P124
Multispeed Ref. 1
-400.0 to 400.0 Hz
3.0 Hz
P125
Multispeed Ref. 2
-400.0 to 400.0 Hz
10.0 (5.0) Hz
P126
Multispeed Ref. 3
-400.0 to 400.0 Hz
20.0 (10.0) Hz
P127
Multispeed Ref. 4
-400.0 to 400.0 Hz
30.0 (20.0) Hz
P128
Multispeed Ref. 5
-400.0 to 400.0 Hz
40.0 (30.0) Hz
P129
Multispeed Ref. 6
-400.0 to 400.0 Hz
50.0 (40.0) Hz
P130
Multispeed Ref. 7
-400.0 to 400.0 Hz
60.0 (50.0) Hz
P131
Multispeed Ref. 8
-400.0 to 400.0 Hz
66.0 (55.0) Hz
P133
Minimum Frequency
0.0 to 400.0 Hz
3.0 Hz
P134
Maximum Frequency
0.0 to 400.0 Hz
66.0 (55.0) Hz
Summary of Contents for CFW300 V1.3X
Page 2: ......
Page 8: ...Contents...
Page 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Page 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Page 72: ...V f Scalar Control 9 10 CFW300 9...
Page 80: ...VVW Vector Control 10 8 CFW300 10...
Page 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Page 132: ...Reading Parameters 15 6 CFW300 15...