Digital and Analog Inputs and Outputs
CFW300 | 12-15
12
d) FORWARD/REVERSE COMMAND
This function is the combination of two DIS: one programmed for forward run and the other for reverse run.
DIx - Forward
DIx - Reverse
Time
Time
Time
Inactive
Inactive
Forward
Reverse
Active
Active
Output
frequency
Figure 12.8:
Example of the Forward /Reverse command
e) START / STOP
This function tries to reproduce the activation of a three-wire direct start with retention contact, where a pulse in
the DIx-Start enables the motor spin while the Dlx-Stop is active.
DIx - Start
DIx - Stop
Time
Time
Time
Inactive
Inactive
Active
Active
Output
frequency
Figure 12.9:
Example of the Start/Stop
NOTE!
All the digital inputs set for General Enable, Fast Stop, Forward Run/Reverse Run and Start/Stop
must be in the "Active" state so that the inverter can enable the motor run.