Digital and Analog Inputs and Outputs
12-18 | CFW300
12
k) 2
nd
RAMP
If DIx is inactive, the inverter uses the default ramp by P100 and P101, otherwise, it will use the 2
nd
Ramp by P102
and P103.
DIx - Run/Stop
DIx - 2
nd
ramp
Time
P103
P102
P101
P100
Time
Inactive
Active
Output
frequency
Time
Active
Inactive
Figure 12.13:
Example of the 2
nd
Ramp function
l) NO EXTERNAL ALARM
If DIx is inactive, the inverter will activate the external alarm A090.
m) NO EXTERNAL FAULT
If DIx is inactive, the inverter will activate the external fault F091. In this case, the PWM pulses are disabled
immediately.
n) FAULT RESET
Once the inverter is with the fault state active, and the fault origin condition is no longer active.
The reset of the fault state will occur when the DIx set for this function is active.
o) DISABLE FLYING START
It allows the DIx, when active, to disable the action of the Flying Start function preset in parameter P320 = 1 or 2.
When the DIx is inactive, the Flying Start function operates normally again. Refer to
.
p) LOCK PROG
When the DIx input is active, parameters cannot be changed, no matter the values set in P000 and P200. When
the DIx input is Inactive, the modification of parameters will depend on the values set in P000 and P200.
q) ACCELERATE E.P. - TURN ON / DECELERATE E.P. - TURN OFF
It consists of the Electronic Potentiometer function with capacity to enable the inverter by means of a pulse at the
start, and a pulse for the stop when the output speed is minimum (P133).
Summary of Contents for CFW300 V1.3X
Page 2: ......
Page 8: ...Contents...
Page 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Page 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Page 72: ...V f Scalar Control 9 10 CFW300 9...
Page 80: ...VVW Vector Control 10 8 CFW300 10...
Page 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Page 132: ...Reading Parameters 15 6 CFW300 15...