SoftPLC
18-16 | CFW300
18
Table 18.11:
Description of the PID controller setpoint automatic adjustment
P930
Description
0
It defines that, in the transition of the PID controller operation mode from manual to automatic, the control setpoint value (P911)
will not be uploaded with the present value of the control process variable (P916), and, in the transition of the PID controller
operation mode from automatic to manual, the setpoint value of the PID controller in manual mode (P918) will not be uploaded
with the present value of the motor speed (P002)
1
It defines that, in the transition of the PID controller operation mode from manual to automatic, the control setpoint value (P911)
will be uploaded with the present value of the control process variable (P916), and, in the transition of the PID controller operation
mode from automatic to manual, the setpoint value of the PID controller in manual mode (P918) will not be uploaded with the
present value of the motor speed (P002)
2
It defines that, in the transition of the PID controller operation mode from manual to automatic, the control setpoint value (P911)
will not be uploaded with the present value of the control process variable (P916), and , in the transition of the PID controller
operation mode from automatic to manual, the setpoint value of the PID controller in manual mode (P918) will be uploaded with
the present value of the motor speed (P002)
3
It defines that, in the transition of the PID controller operation mode from manual to automatic, the control setpoint value (P911)
will be uploaded with the present value of the control process variable (P916), and , in the transition of the PID controller operation
mode from automatic to manual, the setpoint value of the PID controller in manual mode (P918) will be uploaded with the present
value of the motor speed (P002)
P931 – PID Controller Proportional Gain
P932 – PID Controller Integral Gain
P933 – PID Controller Derivative Gain
Adjustable
Range:
0.00 to 99.99
Factory
Setting:
P931 = 1.00
P932 = 5.00
P933 = 0.00
Properties:
Description:
These parameters define the gains of the PID controller and must be set according to the magnitude or process
that is being controlled.
NOTE!
suggests setting values for the gains according to the process to be
controlled by the PID controller.
P934 – PID Controller Sampling Period
Adjustable
Range:
0.050 to 9.999 s
Factory
Setting:
0.100 s
Properties:
Description:
This parameter defines the sampling time of the PID controller.
NOTE!
suggests setting values for the sampling time according to the process to
be controlled by the PID controller.
Summary of Contents for CFW300 V1.3X
Page 2: ......
Page 8: ...Contents...
Page 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Page 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Page 72: ...V f Scalar Control 9 10 CFW300 9...
Page 80: ...VVW Vector Control 10 8 CFW300 10...
Page 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Page 132: ...Reading Parameters 15 6 CFW300 15...