Logical Command and Speed Reference
CFW300 | 7-9
7
P128 - Multispeed Reference 5
Adjustable
Range:
-400.0 to 400.0 Hz
Factory
Setting:
40.0 (30.0) Hz
P129 - Multispeed Reference 6
Adjustable
Range:
-400.0 to 400.0 Hz
Factory
Setting:
50.0 (40.0) Hz
P130 - Multispeed Reference 7
Adjustable
Range:
-400.0 to 400.0 Hz
Factory
Setting:
60.0 (50.0) Hz
P131 - Multispeed Reference 8
Adjustable
Range:
-400.0 to 400.0 Hz
Factory
Setting:
66.0 (55.0) Hz
Properties:
Description:
By the combination of up to three digital inputs, one from eight levels that form the multispeed reference is
selected. Read the description of the of the digital inputs in
Section 12.5 DIGITAL INPUTS on page 12-11
, as well
the reference selection in
Section 7.1 SELECTION FOR LOGICAL COMMAND AND FREQUENCY REFERENCE
. The negative values determine a direction of rotation opposite to that defined by the inverter
command word (bit 2 of P682).
and
show the operation of the Multispeed. Although the most
significant digital input may be set at DI1 or DI2, only one of those options is allowed; otherwise, the Config state
(ConF), according to
Section 5.3 SITUATIONS FOR CONFIG STATUS on page 5-5
, is activated to indicate
parameterization incompatibility.
Summary of Contents for CFW300 V1.3X
Page 2: ......
Page 8: ...Contents...
Page 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Page 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Page 72: ...V f Scalar Control 9 10 CFW300 9...
Page 80: ...VVW Vector Control 10 8 CFW300 10...
Page 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Page 132: ...Reading Parameters 15 6 CFW300 15...