APPENDIX E
xv
BOILER DEFAULT SETTINGS
INDOOR /OUTDOOR RESET MODE
MENU LEVEL
& CODE
DESCRIPTION OF CODE
DEFAULT
VALUE
PRIMARY MENU
tout OUTLET
TEMPERATURE
ACTUAL
Pct
PERCENTAGE OF FIRE RATE
ACTUAL
SEtP UNIT’S
SETPOINT
TEMPERATURE
120
Airt
OUTSIDE AIR TEMPERATURE
ACTUAL
Auto AUTO\MANUAL
MODE
AUTO
ON
SECONDARY MENU
Func
MODE OF OPERATION
OART
rEFt
BUILDING REFERENCE TEMPERATURE
70
rr RESET
RATIO
1.5
OASt
OUTSIDE AIR SENSOR FEATURE
OFF
OAt
OUTSIDE AIR TEMP
0
LLt LOW
LIMIT
TEMPERATURE
40
HLt
HIGH LIMIT TEMPERATURE
220
Pb1 PROPORTIONAL
GAIN
70
Int
INTEGRAL
1
drt DERIVATIVE
0
(off)
Addr ADDRESS
32
LOrE LOCAL/REMOTE
LOC
SECURE MENU
SECr
SECURITY LEVEL
3
Func
MODE OF OPERATION
OART
gAin GAIN
1
Pb3 PROPORTIONAL
BAND
5000
LoFi LOW
FIRE
29
LFti
LOW FIRE TIMER
0
Purg
PURGE
100
O2-O STOP
LEVEL
16%
O2-C START
LEVEL
20%
FLti
FAULT TIMER
0 SEC.
dFiL DISPLAY
FILTER
5
ArUP ANTI
RESET
WINDUP
ON
PEA PEAK
ACTUAL
VAL VALLEY
ACTUAL
InPC INPUT
CORRECTION
0
InPt INPUT
TIMER
0.2
FiLt SENSOR
FILTER
2
Unit
UNIT OF DISPLAY
F
Addr ADDRESS
32
bAUd BAUD
RATE
9600
InP INPUT
CAL