1.2.2
Output limitations due to gas feed pressure and lower
heating value
Fig 1-2
Output limitation factor due to gas feed pressure / LHV
Notes:
No compensation (uprating) of the engine output
is allowed, neither for gas feed pressure higher
than required in the graph above nor lower heating
value above 36 MJ/m
3
N
.
The above given values for gas feed pressure
(absolute pressure) are at engine inlet. The pres-
sure drop over the gas valve unit (GVU) is approx.
80 kPa.
Values given in m
3
N
are at 0°C and 101.3 kPa.
Wärtsilä 50DF Product Guide - a16 - 9 September 2016
1-3
1. Main Data and Outputs
Wärtsilä 50DF Product Guide