Gas mode
Fig 2-4
Maximum instant load steps in % of MCR in gas mode
●
Maximum step-wise load increases according to figure
●
Steady-state frequency band
≤
1.5 %
●
Maximum speed drop 10 %
●
Recovery time
≤
10 s
●
Time between load steps
≥
30 s
●
Maximum step-wise load reductions: 100-75-45-0%
Diesel mode
●
Maximum step-wise load increase 33% of MCR
●
Steady-state frequency band
≤
1.0 %
●
Maximum speed drop 10 %
●
Recovery time
≤
5 s
●
Time between load steps
≥
10 s
Start-up
A stand-by generator reaches nominal speed in 50-70 seconds after the start signal (check
of pilot fuel injection is always performed during a normal start).
With black-out start active nominal speed is reached in about 25 s (pilot fuel injection disabled).
The engine can be started with gas mode selected provided that the engine is preheated and
the air receiver temperature is at required level. It will then start on MDF and gas fuel will be
used as soon as the pilot check is completed and the gas supply system is ready.
Start and stop on heavy fuel is not restricted.
Wärtsilä 50DF Product Guide - a16 - 9 September 2016
2-5
2. Operating Ranges
Wärtsilä 50DF Product Guide
Summary of Contents for WARTSILA 50DF
Page 1: ...WÄRTSILÄ 50DF PRODUCT GUIDE ...
Page 14: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 58: ...This page intentionally left blank ...
Page 102: ...This page intentionally left blank ...
Page 120: ...This page intentionally left blank ...
Page 154: ...This page intentionally left blank ...
Page 164: ...This page intentionally left blank ...
Page 176: ...This page intentionally left blank ...
Page 214: ...This page intentionally left blank ...
Page 232: ...This page intentionally left blank ...
Page 234: ...This page intentionally left blank ...
Page 237: ......
Page 238: ......
Page 239: ......