Emergency stop mode
The sequence of engine stopping in emergency stop mode is similar to shutdown mode,
except that also the pilot fuel injection is de-activated immediately upon stop signal.
Emergency stop is the fastest way of manually shutting down the engine. In case the emergency
stop push-button is pressed, the button is automatically locked in pressed position.
To return to normal operation the push button must be pulled out and alarms acknowledged.
14.2.5
Speed control
Main engines (mechanical propulsion)
The electronic speed control is integrated in the engine automation system.
The remote speed setting from the propulsion control is an analogue 4-20 mA signal. It is also
possible to select an operating mode in which the speed reference can be adjusted with
increase/decrease signals.
The electronic speed control handles load sharing between parallel engines, fuel limiters, and
various other control functions (e.g. ready to open/close clutch, speed filtering). Overload
protection and control of the load increase rate must however be included in the propulsion
control as described in the chapter "Operating ranges".
For single main engines a fuel rack actuator with a mechanical-hydraulic backup governor is
specified. Mechanical back-up can also be specified for twin screw vessels with one engine
per propeller shaft. Mechanical back-up is not an option in installations with two engines
connected to the same reduction gear.
Generating sets
The electronic speed control is integrated in the engine automation system.
The load sharing can be based on traditional speed droop, or handled independently by the
speed control units without speed droop. The later load sharing principle is commonly referred
to as isochronous load sharing. With isochronous load sharing there is no need for load
balancing, frequency adjustment, or generator loading/unloading control in the external control
system.
In a speed droop system each individual speed control unit decreases its internal speed
reference when it senses increased load on the generator. Decreased network frequency with
higher system load causes all generators to take on a proportional share of the increased total
load. Engines with the same speed droop and speed reference will share load equally. Loading
and unloading of a generator is accomplished by adjusting the speed reference of the individual
speed control unit. The speed droop is normally 4%, which means that the difference in
frequency between zero load and maximum load is 4%.
In isochronous mode the speed reference remains constant regardless of load level. Both
isochronous load sharing and traditional speed droop are standard features in the speed
control and either mode can be easily selected. If the ship has several switchboard sections
with tie breakers between the different sections, then the status of each tie breaker is required
for control of the load sharing in isochronous mode.
14.3
Alarm and monitoring signals
Regarding sensors on the engine, please see the internal P&I diagrams in this product guide.
The actual configuration of signals and the alarm levels are found in the project specific
documentation supplied for all contracted projects.
14-12
Wärtsilä 50DF Product Guide - a16 - 9 September 2016
Wärtsilä 50DF Product Guide
14. Automation System
Summary of Contents for WARTSILA 50DF
Page 1: ...WÄRTSILÄ 50DF PRODUCT GUIDE ...
Page 14: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 58: ...This page intentionally left blank ...
Page 102: ...This page intentionally left blank ...
Page 120: ...This page intentionally left blank ...
Page 154: ...This page intentionally left blank ...
Page 164: ...This page intentionally left blank ...
Page 176: ...This page intentionally left blank ...
Page 214: ...This page intentionally left blank ...
Page 232: ...This page intentionally left blank ...
Page 234: ...This page intentionally left blank ...
Page 237: ......
Page 238: ......
Page 239: ......