8.3 Positioning and Installation
The UPS must be installed indoor, in a clean and dry room, preferably without dust or humidity
infiltrations. For the environmental conditions in the place of installation, in compliance with the current
legislation, please refer to the “Overall dimensions, minimum distances from the walls and ventilation”
section.
Special environmental conditions
It is necessary to implement specific protective measures in case of unusual environmental
conditions:
harmful smoke, dust, abrasive dust;
humidity, vapour, salt air, bad weather or dripping;
explosive dust and gas mixture;
extreme temperature variations;
bad ventilation;
conductive or radiant heat from other sources;
fungus, insects, vermin.
8.3.1 Base Plan, Static Load and Weights
Picture 3 – Base plan
The supporting base of the UPS must be designed to carry the UPS weight and to ensure its steady
and safe support.
Its carrying capacity must be adequate to the static loads indicated in the table below.
Power (kVA)
60
80
100
125
160
Weight w/o batteries (kg)
250
300
320
360
380
Static load w/o batteries (kg/m^2)
490
590
630
710
750
Weight with batteries (kg)
800
850
-
-
-
Static load with batteries (kg/m^2)
1570
1670
-
-
-