Wärtsilä JOVYSTAR COMPACT L
BAX 5624
- 80 -
Alarm
A55
PAR CABLE DISC
Description
Parallel cable doesn't communicate.
Possible
causes
Parallel cable disconnected or damaged.
Solutions
1. Check the connection of cable
2. Contact our Technical Support Service.
Alarm
A56
MAINS UNBALANCE
Description
The rectifier input voltage is unbalanced.
Possible
causes
Problems on the LV or MV distribution network
Defect of the measuring circuit
Solutions
1. Check the input voltage
2. Contact our Technical Support Service.
Alarm
A57
INPUT CURRENT UNBALANCED
Description
UPS input currents are not balanced.
Possible
causes
Possible problems in the UPS input stage.
Anomaly of the system control.
Solutions
1. Contact our Technical Support Service.
Alarm
A58
INVERTER CURRENT UNBALANCED
Description
The inverter currents are not balanced.
Possible
causes
Possible problems in the UPS input stage.
Anomaly of the system control.
Solutions
1. Contact our Technical Support Service.
Alarm
A59
BACKFEED RELAY ON
Description
The backfeed protection has been activated. Alarms present only in the history log.
Possible
causes
Problems on the bypass static switch
Solutions
1. Check the static switch thyristors
2. Contact our Technical Support Service.
Alarm
A63
START SEQ BLOCK
Description
During the UPS start-up a failure prevented the proper execution of the sequence.
Possible
causes
Control devices in wrong position or operated improperly.
Possible internal fault.
Solutions
1. Make sure the position of the control devices (isolators, selectors) is as specified
in the procedures (see “Installation and start-up” section).
2. If the alarm persists, contact our Technical Support Service.