9.1.3.6 Ice monitor
Menu item
Setting range Description
Ice monitor ON/OFF
Activate/deactivate the function
Active/inactive when
absent
The automatic control function depends on
the "absent" variable
Status, ice alarm
The current status is loaded from the actua-
tor when the [
Settings
] menu is opened.
To refresh the display, close the [
Settings
]
menu and open it again.
Limit value
0.0...+10.0
°C
If the measured value reaches the limit
value or drops below it, the product moves
to the defined position and slat angle.
End ice alarm
Resets the ice alarm once; the next time it
is called up,
is displayed again
End ice alarm automati-
cally
Defines whether an ice alarm is reset
automatically when the temperature rises at
least three degrees above the defined limit
value
Position
0...100 %
Position to which the product is moved
when the limit value is reached
Slat angle
-180...180°
Slat angle to which a slat product is moved
when the limit value is reached
Measured value outside
temp.
The measured value is loaded from the
actuator when the [
Settings
] menu is
opened. To refresh the display, close the
[
Settings
] menu and open it again.
9.1.3.7 Uemperature control
This menu currently has no function.
Menu item
Setting range Description
Temperature control
ON/OFF
Activate/deactivate control function
Active/inactive when
absent
The automatic control function depends on
the "absent" variable
Limit value, warm
-40.0...+80.0
°C
If this value is reached and exceeded, the
product moves to the defined position and
slat angle
Limit value, cold
-40.0...+80.0
°C
If the measured value reaches the limit
value or drops below it, the product moves
to the defined position and slat angle.
Delay, warm
0...99 min
Waiting period when the limit value is
reached before a move command is
executed
Delay, cold
0...99 min
Waiting period when the limit value is
reached before a move command is
executed
Position, warm
0...100 %
Position to which the product is moved
when the "Warm" limit value is reached
Slat angle, warm
-180...180°
Slat angle to which a slat product is moved
when the "Warm" limit value is reached
Position, cold
0...100 %
Position to which the product is moved
when the "Cold" limit value is reached
Slat angle, cold
-180...180°
Slat angle to which a slat product is moved
when the "Cold" limit value is reached
Main menu
System
Products
Product type
Channel x
Settings
Ice monitor
Main menu
System
Products
Product type
Channel x
Settings
Temperature control