WMS Central transmitter
9.1.3.1 Basic functions
Menu item
Setting range Description
AbsentON/OFF
Condition for automatic control functions
Comfort functions ON/
OFF
Activating or deactivating the comfort func-
tions
9.1.3.2 Sun control
Menu item
Setting range Description
Sun control ON/OFF
Activate/deactivate control function
Adjustable in hand-held
transmitter
Here you can define whether hand-held
transmitters belonging to the network can
be used to influence the control mode
Active/inactive when
absent
The automatic control function depends on
the "absent" variable
Limit value, sun
1...100 klx
If this value is reached and exceeded, the
product moves to the defined position and
slat angle
Limit value, cloud
1...100 klx
If the measured value reaches the limit
value or drops below it, the product moves
to the defined position and slat angle.
Delay, sun
0...99 min
Waiting period when the limit value is
reached before a move command is
executed
Delay, cloud
0...99 min
Waiting period when the limit value is
reached before a move command is
executed
Position, sun
0...100 %
Position to which the product is moved if
the "Sun" limit value is reached
Slat angle sun
-180...180°
Slat angle to which a slat product is moved
when the "Sun" limit value is reached
Position cloud
0...100 %
Position to which the product is moved
when the "Cloud" limit value is reached
Slat angle cloud
-180...180°
Slat angle to which a slat product is moved
when the "Cloud" limit value is reached
Measured value, photo
The measured value is loaded from the
actuator when the [
Settings
] menu is
opened. To refresh the display, close the
[
Settings
] menu and open it again.
Main menu
System
Products
Product type
Channel x
Settings
Basic functions
Main menu
System
Products
Product type
Channel x
Settings
Sun control
System