890405_d•en•2015-12-01
We reserve the right to carry out improvements
90
WMS Central transmitter
Menu item
Setting range Description
Limit value
0...199 mm/h
If this value is reached and exceeded, the
product moves to the defined position and
slat angle
Switch-off delay
0...99 min
Waiting time after the measured value
drops below the limit value before the prod-
uct can be moved again
Position
0...100 %
Position to which the product is moved
when the limit value is reached
Slat angle
-180...180°
Slat angle to which a slat product is moved
when the limit value is reached
Precipitation, manual
override
Defines whether the product can be moved
manually although the precipitation monitor
is still active
Measured value, pre-
cipitation
The measured value is loaded from the
actuator when the [
Settings
] menu is
opened. To refresh the display, close the
[
Settings
] menu and open it again.
9.1.3.5 Wind monitor
Menu item
Setting range Description
Wind monitor ON/OFF
Activate/deactivate the function
Adjustable in hand-held
transmitter
Here you can define whether hand-held
transmitters belonging to the network can
be used to influence the control mode
Active/inactive when
absent
The automatic control function depends on
the "absent" variable
Limit value
0...25 m/s
If this value is reached and exceeded, the
product moves to the defined position and
slat angle
Delay
0...99 s
Waiting period when the limit value is
reached before a move command is
executed
Switch-off delay
0...99 min
Waiting time after the measured value
drops below the limit value before the prod-
uct can be moved again
Position
0...100 %
Position to which the product is moved
when the limit value is reached
Slat angle
-180...180°
Slat angle to which a slat product is moved
when the limit value is reached
Measured value, wind
The measured value is loaded from the
actuator when the [
Settings
] menu is
opened. To refresh the display, close the
[
Settings
] menu and open it again.
Main menu
System
Products
Product type
Channel x
Settings
Wind monitor
System