8.1.5 Sensor compensation
This menu serves to calibrate the internal and external sensors of your Wiso-
tronic to the temperatures measured on site. This may become necessary if
a sensor was mounted in an unfavourable location (such as in the vicinity of
a heat source or in direct sunlight).
Open the following menu: [
Project setup
] > [
System
] >
[
Sensor compensation
].
The following menu appears where the max. possible number of sensors for
temperature is indicated:
8.1.5.1 Control panel temperature
The [
Control panel temperature
] value specifies by how many degrees
Celsius the measured value of the internal sensor of the Wisotronic is cor-
rected up or down. The setting range is –10 °C to +10 °C.
Turn the touch wheel to set the value [
Control panel temperature]
.
The [
Stand.
] function button sets the value to the factory setting.
8.1.5.2 Weather station 1 (2,3)
outside temperature
The [
Multisense 1 Outside temperature
] value specifies by how many
degrees Celsius the measured value of weather station 1 is corrected up or
down. The setting range is –30...+10 °C.
Turn the touch wheel to set the value [
Multisense 1 Outside temp.
].
The [
Stand.
] function button sets the value to the factory setting.
Weather stations 2 and 3 are not available for Wisotronic 1-channel.
When commissioning, note that the weather station multisense has an inter-
nal temperature correction feature that improves measurement accuracy. The
device follows temperature changes at a rate of approx. 10 min per °C.
When the Wisotronic is first switched on, the first temperature measurement
is taken at the weather station multisense. If the weather station was previ-
ously stored at a considerably lower or higher temperature, it may take sev-
eral hours before the correct temperature is displayed.
If the weather station is already at the temperature of its environment when
the Wisotronic is first switched on, the actual temperature measurement
value will be displayed from the start.
Main menu
Settings
Service
Project setup
System
Sensor compensation
System settings