PROFINET IO 750-340
I/O Device Configuration
WAGO-I/O-SYSTEM
750
PROFINET IO
3.1.3.3.2
Standard Module Parameters
Certain characteristics of some I/O modules can be parameterized during the
configuration. At present, this only applies to the output modules whose
substitute value behavior can be set independent of the modules used.
Parameter
Setting
Description
Substitute value
behavior
of the outputs
In case the I/O controller does not
supply valid output data for the
module or the group of modules then
according to the device
settings*)
the set strategy on the side of the
station substitute applies (I/O
device).
according to the
referenced module
settings*)
2
)
the set strategy on the side of the
referenced digital module by which
the output data has been reserved.
These settings apply to digital output
modules without process data. These
are characterized using a * behind
the item number.
Output values are set
to 0
all outputs are immediately reset
Outputs maintain the
last valid value
all outputs maintain the last valid
value
outputs take on their
default value
all outputs switch to their configured
substitute value
*) Presetting
2) Digital modules whose process data has been allocated
to their previous slots implicitly take over the default
value strategy of the module on the slot allocated.