90
•
PROFINET IO 750-340
Diagnostics
WAGO-I/O-SYSTEM
750
PROFINET IO
Fault type "Configuration fault" (0x0010)“
Extended
fault type
Additional
value
Description
0x0097
0xC0018097 The reserved station parameters (Table 0, register 2) have
invalid values.
0x0098
0xC0018098 The settings for the internal data bus extension (Table 0,
register 2) is not allowed.
0x0099
0xC0018099 The reserved station parameters (Table 0, register 3) have
invalid values.
0x009A
0xC001809A The connection for creating the process image (Table 0,
register 3) is deactivated.
0x009B
0xC001809B The algorithm for creating the process image (Table 0, register
3) is not allowed.
0x009C
0xC001809C The integration of control and status data of complex modules
(Table 0, register 3) is activated.
0x009D
0xC001809D Formatting of complex module data (Table 0, register 3) is not
allowed.
0x009E
0xC001809E Formatting of digital module data (Table 0, register 3) is not
allowed.
0x009F
0xC001809F The data allocation (Table 0, register 3) is not allowed (neither
bytes nor words).
0x00A0
0xC00180A0 The setting for updating the input data (Table 0, register 3) is
not allowed (not asynchronous).
0x00A1
0xC00180A1 The setting for updating the output data (Table 0, register 3) is
not allowed (not asynchronous).
0x00A2
0xC00180A2 The settings for the behavior of fieldbus faults (Table 0,
register 3) is not allowed.
0x00A3
0xC00180A3 The settings for the behavior of internal data bus faults (Table
0, register 3) is not allowed.
0x00A4
0xC00180A4 The settings for activating the diagnostics (Table 0, register 3)
is not allowed.
0x00A5
0xC00180A5 The linking of the diagnostics data to the process image (Table
0, register 3) is activated.
0x00A6
0xC00180A6 The reserved station parameters (Table 0, register 4) have
invalid values.
... ...
...
0x00B2
0xC00180B2 The reserved station parameters (Table 0, register 4) have
invalid values.
0x00B3
0xC00180B3 The reserved station parameter (Table 100, register 75) have
invalid values.
0x00B4
0xC00180B4 The module setting (Table 100, register 75) is not allowed.
0x00B5
0xC00180B5 The reserved station parameter (Table 100, register 76) have
invalid values.
0x00B6
0xC00180B6 The reserved station parameter (Table 100, register 77) have
invalid values.