56
•
PROFINET IO 750-340
I/O Device Configuration
WAGO-I/O-SYSTEM
750
PROFINET IO
3.1.3.3 Parameter
Setting
3.1.3.3.1 Station
Parameters
The parameters of the station substitute are used to set the overall settings of
the PROFINET IO node. Some of the settings are used in the modules as
default settings and can be optionally overwritten within the module
configuration.
Parameter
Setting
Description
Restart of the internal data bus
following a fault, such as, for
example, no end module following
POWER ON RESET*)
after an interruption of the buscoupler
supply
Restart the internal
bus after a fault
AUTORESET
immediately after overcoming the
internal bus fault
Use of the internal data bus extension
EEPROM setting*)
Based upon the settings made in
EEPROM that are made using the
"WAGO Extension Settings" tool.
not used
is excluded
Internal Data Bus
Extension
used
is possible
The external diagnostics information
of all diagnostics capable I/O modules
are
locked
not transferred to the PROFINET
I/O Controller
Message external
module / channel
fault
released*)
transferred to the PROFINET
I/O Controller
Word or double word orientated
process data are transfered to the
PROFINET I/O Controller in:
INTEL (LSB-MSB)
"Little Endian" format
Process value
display
MOTOROLA (MSB-
LSB)*)
"Big Endian" format