PROFINET IO 750-340
•
79
Diagnostics
WAGO-I/O-SYSTEM 750
PROFINET IO
Identifier
Description
0x0010 Channel
Diagnostics
0x8104
Deviating set / actual configuration
The version enables you to see if the process type (Application Process
Identifier – API) follows immediately after the head structure or not.
Version
Description
1.0
Data set does not contain the API
1.1
Data set contains the API
The head of the structure has a length of 6 bytes and is composed of as
follows:
Byte
offset
Data type
Description
0 / 1
WORD
Database contents
0x0010 Channel
Diagnostics
0x8104 Deviating
set
/ actual configuration
2 / 3
WORD
Length of the data sets in bytes
Length of the version in bytes including
BYTE 0x01
Version (major) = 1
4/5
BYTE
Version (minor)
0 Diagnostics data will follow at the end
1 API will follow at the end
6 / 7
DWORD
0x00
0x00
API = 0
8 / 9
0x00
0x00
Only available in version 1,1
The process type API has a data length of 4 bytes. Depending on the version
of the data set, the diagnostics data follow with Byteoffset 6 (Version 1.0) or
Byteoffset 10 (Version 1.1). However, the description of the diagnostics data
in the sub-chapters - depending on the
BlockType
- begins back with
Byteoffset 0.
3.1.7.2.1
Channel Specific Diagnostics
Errors occurring when configuring and setting the parameters of the station
(I/O device) and the connected I/O modules as well as external errors from the
connected periphery are reported by the coupler via channel specific
diagnostics. External errors reported by the subassemblies (e.g. short circuits,
line interruptions) are only transmitted to the I/O controller after release when
setting the module's parameters.