I/O Modules • 215
Configuration and Parameter Setting of the Modules
WAGO-I/O-SYSTEM 750
PROFINET IO
5.3.7 Sytem
Modules
5.3.7.1
Supply Modules with 2 Bit Diagnostics Status
Instances
PNIO
Module type
Module type member
PNIO-Data type
Input
Output
2DIA DIA_0
- -
-
2 DIA(+6 BIT I),
DIA in E-PA
PE_DIA_8
Unsigned 8-bit
field
1 -
2DIA(+14 BIT I),
DIA in E-PA
PE_DIA_16
Unsigned 16-bit
field
1 -
2DIA(+30 BIT I),
DIA in E-PA
PE_DIA_32
75x-610, 75x-611
Unsigned 32-bit
field
1 -
* 2DIA(-2 BIT I),
DIA in E-PA
PE_DIA_0
75x-610*, 75x-611*
-
- -
Inputs
Bit allocation
PNIO
Module type
Length
[Bit]
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Note
D0
2DIA(+6 BIT I),
DIA im E-PA
2DIA(+14 BIT I),
DIA im E-PA
2DIA(+30 BIT I),
DIA im E-PA
2
8, 16 or 32 bits are applied in the input
process image of the station proxy (fieldbus
coupler) by fitting a slot with these modules.
The bits 2
0
and 2
1
in the input area are
assigned with the diagnostics condition of
the physically connected supply module. The
bits 2
2
to 2
7
, 2
15
or 2
31
marked green are
made available for the input and / or
diagnostics information of the following
modules. One byte process data qualifier
(IOPS) is managed in the direction of the I/O
control in the cyclic POFINET IO telegram
for these modules.
D0
D0
▪
▪
▪
* 2DIA(-2 BIT I),
DIA in E-PA
2
D0
The fitting of slots with this module enables
the remaining bit locations to be previously
filled with input modules without bytes
opened with star (bit fields) in the input
process image of the station proxy(fieldbus
coupler). One byte process data qualifier
(IOPS) is managed in the direction of the I/O
controller in the cyclic PROFINET IO
telegram for these modules.