I/O Modules • 209
Configuration and Parameter Setting of the Modules
WAGO-I/O-SYSTEM 750
PROFINET IO
5.3.5.5
Digital Impulse Interface
Instances
PNIO
Module type
Module type member
PNIO-Data type
Input
Output
1DII
75x-635
Unsigned 8
Unsigned 8[3]
1 1
Inputs
Bit allocation
PNIO
Module type
Length
[Bit]
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Note
PD
RA
F
Status 0 / Register RES
Channel 0 / Table 0
Input data
channel 0 Byte 0
Register date RD
Table 0, LB
Input data
channel 0 Byte 1
Register date RD
Table 0, HB
Input data
channel 0 Byte 2
4
\ - - - - - - - - - - - - - - Input - - - - - - - - - - - - - - /
PD
RA
RW
Control 0 / Register REQ
Channel 0 / Table 0
Output data
channel 0 Byte 0
Register date WR
Table 0, LB
Output data
channel 0 Byte 1
Register date WR
Table 0, HB
Output data
channel 0 Byte 2
1DII
4
\ - - - - - - - - - - - - - - Output - - - - - - - - - - - - - - /
2 byte and 1 word (4 byte) are applied in the
output process image of the station proxy
(fieldbus coupler) are assigned to the
physical module by fitting the slot with this
module. The quality rating of the bytes
within the word is a result of the selected
data format. This module enables access to
the register structure of the I/O module for
configuration purposes. Two byte process
data qualifiers (IOPS, IOCS) are managed in
the direction of the I/O controller in the
cyclic PROFINET IO telegram for this
module.
Parameter
Value
Significance
Asynchronous diagnostic
message
channel x
The following occurs per diagnostics data sets and
diagnostics alarm with external faults
locked*)
•
not transferred to the I/O Controller
released
•
transferred to the I/O Controller
*) Default settings