I/O Modules • 175
Configuration and Parameter Setting of the Modules
WAGO-I/O-SYSTEM 750
PROFINET IO
Parameter
Value
Significance
Asynchronous diagnostics
message
Channel x (x = 0.1)
With external faults, channel diagnostics and the
respective alarms are
locked*)
•
not transferred to the I/O controller
released
•
transferred to the I/O controller
Substitute value behavior of the
outputs
In case the I/O controller does not supply valid
output data for the module or the group of modules
then
according to the device settings*)
•
the set strategy on the side of the station
substitute applies (I/O device).
Outputs are set to 0
•
all outputs are immediately reset
Outputs maintain the last valid
value
•
all outputs maintain the last valid value
Outputs take on their substitute
value
•
all outputs switch to their configured substitute
value
Substitute output status channel
x
(x = 0.1)
0
*)
1
When configuring the substitute value behavior on
the side of the I/O module, these values are
transmitted to the binary signal channel with invalid
output states of the I/O controller.
*) Default settings