170 •
I/O Modules
Configuration and Parameter Setting of the Modules
WAGO-I/O-SYSTEM
750
PROFINET IO
5.3.2.2
2 (1)-Channel Digital Output Modules with 1 Bit Diagnostics Status per
Channel
Instances
PNIO
Module type
EA Type
Module type member
PNIOdata type
Input
Output
2DA(+6 BIT O)
DO_8
- 1
2DA(+6 BIT I/O),
DIA in E-PA
DO_DIA_8
Unsigned 8-Bit
field
1 1
2DA(+14 BIT O)
DO_16
- 1
2DA(+12 BIT I/O),
DIA in E-PA
DO_DIA_16
Unsigned 16-Bit
field
1 1
2DA(+30 BIT O)
DO_32
- 1
2DA(+28 BIT I/O),
DIA in E-PA
DO_DIA_32
75x-507, 75x-522, 75x-523 (1 DO)
Unsigned 32-Bit
field
1 1
* 2DA(-2 BIT O)
DO_0
* 2DA(-2 BIT I/O),
DIA in E-PA
DO_DIA_0
75x-507*, 75x-522*, 75x-523* (1 DO)
- -
-
Inputs
Bit allocation
PNIO
Module type
Length
[Bit]
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Note
A1
A0
\ - - - - - - - - - - - - - - Output - - - - - - - - - - - - - - /
2DA(+6 BIT O)
2DA(+14 BIT O)
2DA(+30 BIT O)
2
8, 16 or 32 bits are applied in the output
process image of the station proxy (fieldbus
coupler) by fitting a slot with these modules.
The bits 2
0
and 2
1
are assigned with the
signal condition of the physically connected
I/O module. The bits 2
2
to 2
7
, 2
15
or 2
31
marked green are made available for the
output and / or confirmation information of
the following modules. One byte process data
qualifier (IOCS) is managed in the direction
of the I/O controller in the cyclic PROFINET
IO telegram for these modules.
A1
A0
2
\ - - - - - - - - - - - - - - Output - - - - - - - - - - - - - - /
D1
D0
\ - - - - - - - - - - - - - - Input - - - - - - - - - - - - - - /
2DA(+6 BIT I/O),
DIA inE-PA
2DA(+14 BIT I/O),
DIA in E-PA
2DA(+30 BIT I/O),
DIA in E-PA
2
8, 16 or 32 bits are applied in the input and
output process image of the station proxy
(fieldbus coupler) by fitting a slot with these
modules. The bits 2
0
and 2
1
in the output area
are assigned with the signal condition of the
physically connected I/O module. The bits 2
2
to 2
7
, 2
15
or 2
31
marked green are made
available for the output and / or confirmation
information of the following modules. The
bits 2
0
and 2
1
in the input area are assigned
with the diagnostics condition of the
physically connected I/O module. The bits
marked green are made available for the
input and / or diagnostics information of the
following module slots. Two byte process
data qualifiers (IOCS, IOPS) are managed in
the transmission direction of the I/O
controller in the cyclic PROFINET IO
telegram for this module.