PROFINET IO 750-340
•
75
Process Image
WAGO-I/O-SYSTEM 750
PROFINET IO
3.1.5.3 Example
The allocation should become clear by way of a fieldbus node with a coupler
and 17 I/O modules.
402
DI DI
DI DI
DI DI
402
402
452
602
504
504
530
530
602
602
600
550
550
452
452
504
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
PROFINET
AI AI
DO DO
DO DO DO DO DO DO
DO DO DO DO
AO AO
AI AI
AO AO AI AI
DO DO
750-340
Fig. 3.1.5-8: Application example
g012115x
No.
I/O module
Module
PA I/O Controller *
Identifier
Inputs
Outputs
Digital input
E 12.0
---
Digital input
E 12.1
---
Digital input
E 12.2
---
1
Digital input
75x-402 4DE(+4 BIT E)
(UINT8 IN)
E 12.3
---
Digital input
E 12.4
---
Digital input
E 12.5
---
Digital input
E 12.6
---
2
Digital input
75x-402* 4DE(-4 BIT E)
(-)
E 12.7
---
Digital input
E 13.0
---
Digital input
E 13.1
---
Digital input
E 13.2
---
3
Digital input
75x-402 4DE(+12 BIT E)
(UINT16 IN)
E 13.3
---
Analog input
EW 256
---
4
Analog input
750-452 2AE, 0-20 mA
(INT16[2] IN)
EW 258
---
5 Supply
750-610 Supply, DIA
(-)
--- ---
Digital output
---
A 8.0
Digital output
---
A 8.1
Digital output
---
A 8.2
6
Digital output
75x-504 4DA(+28 BIT A)
(UINT32 OUT)
--- A
8.3
Digital output
---
A 8.4
Digital output
---
A 8.5
Digital output
---
A 8.6
7
Digital output
75x-504* 4DA(-4 BIT A)
(-)
--- A
8.7