765-4203/0100-0000
Functions
Product manual | Version: 1.0.0
31
4PORT IOL-A FLD EC DC 24V 2.0A
5.5 Parameterization Tools
5.5.1 Overview
There are several ways to set the product’s parameters. The following table provides an
overview of the tools.
Table 31: Overview of Parameterization Tools
Tool
Description
Controller with EtherCAT
®
Master
The
EtherCAT master
must be configured to exchange process data with the 765
Series modules.
The
WAGO_series765.xml
and
WAGO_series765_diag.xml
device description
files contain the WAGO I/O System Field modules. The configuration software of
the EtherCAT
®
master imports these XML files, and the user can select and param-
eterize a module (or multiple modules) of the 765 Series.
For each of ports X01, X02, ..., the user specifies in the configuration how much
process data the connected IO-Link device transfers, or whether a digital input or
output is connected to the port. The user loads the configuration onto the Ether-
CAT
®
master. The EtherCAT
®
master configures and parameterizes the 765 Series
modules via EtherCAT
®
.
WAGO I/O Field Web-
server
The
WAGO I/O Field Webserver
is a Webserver that is integrated into the 765
Series module. Using a Web browser, the user can view the Web pages and dis-
play and modify parameters.
WAGO I/O Field App
The
WAGO I/O Field app
is an app for mobile devices that can communicate with
a 765 module via Bluetooth
®
. With the app, the user can parameterize the IO-Link
master and the connected IO-Link devices, read and write process data and dis-
play diagnostics.
WAGO IO-Link Configura-
tor
WAGO IO-Link Configurator
is software for configuring the WAGO IO-Link mas-
ter and the IO-Link devices.
Three domains are distinguished for configuration and parameterization:
1. The
EtherCAT configuration
: select EtherCAT
®
module
2. The
port configuration
: IO-Link master (and the amount of IO-Link process data: 1,
2, 4, 8, 16, or 32 bytes), digital input or output.
3. 3: The
IO-Link device configuration
The following table shows which tool can influence which section.
Table 32: Parameterization Overview
Tool
EtherCAT
®
Module
Port Configuration
IO-Link Device Configu-
ration
EtherCAT
®
Master
The EtherCAT
®
master
configures the 765 Series
module.
The EtherCAT
®
master
sets the parameter se-
lected by the user on the
basis of the parameters in
the XML file
WAGO_se-
ries765.xml
. For each
port, the configuration de-
termines whether the port
is used as an IO-Link mas-
ter, a digital input or a digi-
tal output (or is disabled).
-
WAGO I/O Field Web-
server
–
Yes
Input fields to read/write