765-4203/0100-0000
Properties
Product manual | Version: 1.0.0
19
4PORT IOL-A FLD EC DC 24V 2.0A
Property
Value
Output current, L1
Maximum: 4.0 A per channel per IEC 61131-2
Output current, L1 with IO-Link operating mode
Maximum 1.0 A with conductor size AWG 22/0.34 mm
2
and cable length of up to 20 m (per IO-Link specifica-
tion)
Maximum 4.0 A with increased conductor cross-sec-
tion or reduced cable length (max. voltage drop of
1.2 V for both feed and return line individually)
Output current, L2
Maximum: 4.0 A per channel per IEC 61131-2
Output current, L2 with IO-Link operating mode
Maximum 1.0 A with conductor size AWG 22/0.34 mm
2
and cable length of up to 20 m (per IO-Link specifica-
tion)
Maximum 4.0 A with increased conductor cross-sec-
tion or reduced cable length (max. voltage drop of
1.2 V for both feed and return line individually)
Circuit
High-side driver
The 1L+/2L+ output is not resistant to reverse power
feeding.
The input voltage must not exceed the supply voltage.
Self-protection
Overcurrent, overload, overtemperature and overvolt-
age
Voltage drop through high-side path
Less than 200 mV
Maximum capacitive load
1000 μF parallel to 24 Ω; 0.1 Hz
470 μF parallel to 12 Ω; 0.1 Hz
220 μF parallel to 6 Ω; 0.1 Hz
Maximum inductive load
1.15 H / 2 A; 0.2 Hz; DC13
Diagnostics (1L+)
Events: overcurrent, overload, overtemperature and
overvoltage
4.4.4 Power Supply
Table 11: Power supply
Parameters
Value
Supply voltage, 1L, 2L
24 VDC, –25 %/+30 % (18 VDC ... 31.2 VDC)
Voltages above 34 V can permanently damage the de-
vice.
Voltages below approx. 11 V lead to device reset.
Undervoltage warning, 1L
18.0 V (± 5 % at 25 °C) message On,
18.3 V (± 5 % at 25 °C) message Off
Overvoltage warning, 1L
30.0 V (± 5 % at 25 °C) message On,
29.7 V (± 5 % at 25 °C) message Off
Module power consumption
1L: 80 mA (at 24 VDC)
2L: - (at 24 VDC)
Power consumption of supply connections
Max. 16 A; ensure external limitation or use fuses in
the cables.
The maximum total current of the device, including
transmission between the power supply connections,
must not exceed 16 A for both 1L and 2L individually. If
additional modules are connected to X32 (PWR OUT),
it may be necessary for the maximum total current to
be monitored with external power supply management.
Maximum current: Observe derating as a function of
surrounding air temperature.