![WAGO 750-489 Manual Download Page 77](http://html1.mh-extra.com/html/wago/750-489/750-489_manual_868450077.webp)
WAGO-I/O-SYSTEM 750
Process Image 77
750-489 4AI RTD/TC/Strain Gauge Ex i
Manual
Version 1.1.0, valid from FW Version 02
4.6.3.5 TC Type E – Standard Format/Kelvin
Table 79: TC Type E Setting – Standard Format/Kelvin
Temperature
[K]
Numeric Value
Status
Byte,
Hex.
Error
LED
Range
Binary
Hex.
Dec.
≤ 48
.1
'1000.0000.0000.0000'
0x8000 -32768
0x50
On
Underflow
48.2
'0000.0001.1110.0010'
0x01E2
482
0x41
On
Underrange
73.1
'0000.0010.1101.1011'
0x02DB
731
73.2
'0000.0010.1101.1100'
0x02DC
732
0x00
Off
Nominal
range
1273.2
'0011.0001.1011.1100'
0x31BC 12732
1273.3
'0011.0001.1011.1101'
0x31BD 12733
0x42
On
Overrange
1298.2
'0011.0010.1011.0110'
0x32B6 12982
≥ 1298
.3
'0111.1111.1111.1111'
0x7FFF 32767
0x60
On
Overflow
4.6.3.6 TC Type E – S5-FB250 Format/Kelvin
Table 80: TC Type E Setting – S5-FB250 Format/Kelvin
Temperature
[K]
Numeric Value
Status
Byte,
Hex.
Error
LED
Range
Binary
XFÜ
1)
Hex.
Dec.
≤ 47
.0
'1000.0000.0000.0 010'
0x8002
-32766
0x50
On
Underflow
48.0
'0000.0001.1000.0 001'
0x0181
385
0x41
On
Underrange
72.0
'0000.0010.0100.0 001'
0x0241
577
73.0
'0000.0010.0100.1 000'
0x0248
584
0x00
Off
Nominal
range
1273.0
'0010.0111.1100.1 000'
0x27C8
10184
1274.0
'0010.0111.1101.0 001'
0x27D1
10193
0x42
On
Overrange
1298.0
'0010.1000.1001.0 001'
0x2891
10385
≥ 1299
.0
'0111.1111.1111.1 010'
0x7FFA
32762
0x60
On
Overflow
1)
Status bits: X= not used, F= error, Ü= overflow