The context menu (right mouse button) gives you the following options:
•
Print Table…
•
Copy Equation
•
Copy Multiplier
Figure 35: Context Menu
Example formulas for the conversion:
• Temperature Measurements
Standard format
T(x) = x * 0.1
Standard format, high resolution
T(x) = x * 0.01
S5-FB250
T(x) = x * 0.125
S5-FB250, high resolution
T(x) = x * 0.0125
• Voltage Measurements
Example:
±30 mV
Standard format
U(x) = x * 0.0012
S5-FB250
U(x) = x * 0.0015
Example:
SG - U
ref
: 2.4 V
Standard format
U(x) = x * 0.1
S5-FB250
U(x) = x * 0.125
Example:
SG - U
d
: ±15 mV
Standard format
U(x) = x * 0.0006
S5-FB250
U(x) = x * 0.00075
• Resistance
Example:
0-250
Ω
Standard format
R(x) = x * 0.01
S5-FB250
R(x) = x * 0.0125
• Potentiometer
Standard format
f(x) = x * 0.005
S5-FB250