WAGO-I/O-SYSTEM 750
Process Image 69
750-489 4AI RTD/TC/Strain Gauge Ex i
Manual
Version 1.1.0, valid from FW Version 02
4.5.3.15 TC Type T – Standard Format/Fahrenheit
Table 65: TC Type T Setting – Standard Format/Fahrenheit
Temperature
[°F]
Numeric Value
1)
Status
Byte,
Hex.
Error
LED
Range
Binary
Hex.
Dec.
≤
-373.1
'1000.0000.0000.0000'
0x8000 -32768
0x50
On
Underflow
-373.0
'1111.0001.0110.1110'
0xF16E
-3730
0x41
On
Underrange
-328.1
'1111.0011.0010.1111'
0xF32F
-3281
-328.0
'1111.0011.0011.0000'
0xF330
-3280
0x00
Off
Nominal
range
752.0
'0001.1101.0110.0000'
0x1D60
7520
752.1
'0001.1101.0110.0001'
0x1D61
7521
0x42
On
Overrange
797.0
'0001.1111.0010.0010'
0x1F22
7970
≥
797.1
'0111.1111.1111.1111'
0x7FFF 32767
0x60
On
Overflow
1)
Process values below 0 are represented in binary form as the two’s complement.
4.5.3.16 TC Type T – S5-FB250 Format/Fahrenheit
Table 66: TC Type T Setting – S5-FB250 Format/Fahrenheit
Temperature
[°F]
Numeric Value
Status
Byte,
Hex.
Error
LED
Range
Binary
XFÜ
1)
Hex.
Dec.
≤
-374.0
'1000.0000.0000.0 010'
0x8002
-32766
0x50
On
Underflow
-373.0
'1111.0100.0101.1 001'
0xF459
-2983
0x41
On
Underrange
-329.0
'1111.0101.1011.1 001'
0xF5B9
-2631
-328.0
'1111.0101.1100.0 000'
0xF5C0
-2624
0x00
Off
Nominal
range
752.0
'0001.0111.1000.0 000'
0x1780
6016
753.0
'0001.0111.1000.1 001'
0x1789
6025
0x42
On
Overrange
797.0
'0001.1000.1110.1 001'
0x18E9
6377
≥
798.0
'0111.1111.1111.1 010'
0x7FFA
32762
0x60
On
Overflow
1)
Status bits: X= not used, F= error, Ü= overflow