![WAGO 750-489 Manual Download Page 55](http://html1.mh-extra.com/html/wago/750-489/750-489_manual_868450055.webp)
WAGO-I/O-SYSTEM 750
Process Image 55
750-489 4AI RTD/TC/Strain Gauge Ex i
Manual
Version 1.1.0, valid from FW Version 02
4.4.3.13 TC Type R and Type S – Standard Format/Celsius
Table 39: TC Type R and Type S Setting – Standard Format/Celsius
Temperature
[°C]
Numeric Value
1)
Status
Byte,
Hex.
Error
LED
Range
Binary
Hex.
Dec.
≤
-75.1
'1000.0000.0000.0000'
0x8000 -32768
0x50
On
Underflow
-75.0
'1111.1101.0001.0010'
0xFD12
-750
0x41
On
Underrange
-50.1
'1111.1110.0000.1011'
0xFE0B
-501
-50.0
'1111.1110.0000.1100'
0xFE0C
-500
0x00
Off
Nominal
range
1768.0
'0100.0101.0001.0000'
0x4510
17680
1768.1
'0100.0101.0001.0001'
0x4511
17681
0x42
On
Overrange
1793.0
'0100.0110.0000.1010'
0x460A 17930
≥ 1793.1
'0111.1111.1111.1111'
0x7FFF 32767
0x60
On
Overflow
1)
Process values below 0 are represented in binary form as the two’s complement.
4.4.3.14 TC Type R and Type S – S5-FB250 Format/Celsius
Table 40: TC Type R and Type S Setting – S5-FB250 Format/Celsius
Temperature
[°C]
Numeric Value
Status
Byte,
Hex.
Error
LED
Range
Binary
XFÜ
1)
Hex.
Dec.
≤
-76.0
'1000.0000.0000.0 010'
0x8002
-32766
0x50
On
Underflow
-75.0
'1111.1101.1010.1 001' 0xFDA9
-599
0x41
On
Underrange
-51.0
'1111.1110.0110.1 001'
0xFE69
-407
-50.0
'1111.1110.0111.0 000'
0xFE70
-400
0x00
Off
Nominal
range
1768.0
'0011.0111.0100.0 000'
0x3740
14144
1769.0
'0011.0111.0100.1 001'
0x3749
14153
0x42
On
Overrange
1793.0
'0011.1000.0000.1 001'
0x3809
14345
≥ 1794.0
'0111.1111.1111.1 010'
0x7FFA
32762
0x60
On
Overflow
1)
Status bits: X= not used, F= error, Ü= overflow