58 Process Image
WAGO-I/O-SYSTEM 750
750-489 4AI RTD/TC/Strain Gauge Ex i
Manual
Version 1.1.0, valid from FW Version 02
4.4.4.2 S5-FB250 Format/Celsius
The temperature values are displayed at a resolution of one digit per 0.1 °C.
The status information is represented in bit 0 to bit 2 and the digitized measured
value in bit 3 to bit 15.
Table 45: Temperature Measurement Setting with High Resolution Option – S5-FB250 Format/
Celsius
Temperature
[°C]
Numeric Value
Status
Byte,
Hex.
Error
LED
Range
Binary
XFÜ
1)
Hex.
Dec.
≤
-60.1
'1000.0000.0000.0 010'
0x8002
-32766
0x50
On
Underflow
-60.0
'1110.1101.0100.0 001' 0xED41
-4799
0x41
On
Underrange
-50.1
'1111.0000.0101.1 001'
0xF059
-4007
-50.0
'1111.0000.0110.0 000'
0xF060
-4000
0x00
Off
Nominal
range
150.0
'0010.1110.1110.0 000'
0x2EE0
12000
150.1
'0010.1110.1110.1 001'
0x2EE9
12009
0x42
On
Overrange
160.0
'0011.0010.0000.0 001'
0x3201
12801
≥ 160.1
'0111.1111.1111.1 010'
0x7FFA
32762
0x60
On
Overflow
1)
Status bits: X= not used, F= error, Ü= overflow
Table 46: Type C TC Setting with High Resolution Option – S5-FB250 Format/Celsius
Temperature
[°C]
Numeric Value
Status
Byte,
Hex.
Error
LED
Range
Binary
XFÜ
1)
Hex.
Dec.
≤
-10.1
'1000.0000.0000.0 010'
0x8002
32766
0x50
On
Underflow
-10.0
'1111.1100.1110.0 001' 0xFCE1
-799
0x41
On
Underrange
-0.1
'1111.1111.1111.1 001'
0xFFF9
-7
0.0
'0000.0000.0000.0 000'
0x0000
0
0x00
Off
Nominal
range
150.0
'0010.1110.1110.0 000'
0x2EE0
12000
150.1
'0010.1110.1110.1 001'
0x2EE9
12009
0x42
On
Overrange
160.0
'0011.0010.0000.0 001'
0x3201
12801
≥ 160.1
'0111.1111.1111.1 010'
0x7FFA
32762
0x60
On
Overflow
1)
Status bits: X= not used, F= error, Ü= overflow