4.5.4.2 S5-FB250 Format/Fahrenheit
The temperature values are displayed at a resolution of one digit per 0.1 °F.
The status information is represented in bit 0 to bit 2 and the digitized measured
value in bit 3 to bit 15.
Table 69: Temperature Measurement Setting with High Resolution Option – S5-FB250 Format/
Fahrenheit
Temperature
[°F]
Numeric Value
Status
Byte,
Hex.
Error
LED
Range
Binary
XFÜ
1)
Hex.
Dec.
≤
-76,1
'1000.0000.0000.0 010'
0x8002
-32766
0x50
On
Underflow
-76,0
'1110.1000.0100.0 001'
0xE841
-6079
0x41
On
Underrange
-58,1
'1110.1101.1101.1 001' 0xEDD9
-4647
-58,0
'1110.1101.1110.0 000' 0xEDE0
-4640
0x00
Off
Nominal
range
302,0
'0101.1110.0110.0 000'
0x5E60
24160
302,1
'0101.1110.0110.1 001'
0x5E69
24169
0x42
On
Overrange
320,0
'0110.0100.0000.0 001'
0x6401
25601
≥ 320,1
'0111.1111.1111.1 010'
0x7FFA
32762
0x60
On
Overflow
1)
Status bits: X= not used, F= error, Ü= overflow
Table 70: Type C TC Setting with High Resolution Option – S5-FB250 Format/Fahrenheit
Temperature
[°F]
Numeric Value
Status
Byte,
Hex.
Error
LED
Range
Binary
XFÜ
1)
Hex.
Dec.
≤ 13,9
'1000.0000.0000.0 010'
0x8002
32766
0x50
On
Underflow
14,0
'0000.0100.0110.0 001'
0x0461
1119
0x41
On
Underrange
31,9
'0000.1001.1111.1 001'
0x09F9
2551
32,0
'0000.1010.0000.0 000'
0x0A00
2560
0x00
Off
Nominal
range
302,0
'0101.1110.0110.0 000'
0x5E60
24160
302,1
'0101.1110.0110.1 001'
0x5E69
24169
0x42
On
Overrange
320,0
'0110.0100.0000.0 001'
0x6401
25601
≥ 320,1
'0111.1111.1111.1 010'
0x7FFA
32762
0x60
On
Overflow
1)