![WAGO 750-489 Manual Download Page 73](http://html1.mh-extra.com/html/wago/750-489/750-489_manual_868450073.webp)
WAGO-I/O-SYSTEM 750
Process Image 73
750-489 4AI RTD/TC/Strain Gauge Ex i
Manual
Version 1.1.0, valid from FW Version 02
4.6.1
Pt100, Pt200, Pt500, Pt1000 (EN 60751)
4.6.1.1 Standard Format/Kelvin
The possible numeric range corresponds to the temperature range from +73.2 K
to +1123.2 K, meaning it ranges from +732 to +11232.
Table 71: Pt100, Pt200, Pt500, Pt1000 (EN 60751) Setting, Standard Format/Kelvin
Temperature
[K]
Numeric Value
Status
Byte,
Hex.
Error
LED
Range
Binary
Hex.
Dec.
≤ 48
.1
'1000.0000.0000.0000' 0x8000
-32768
0x50
On
Underflow
48.2
'0000.0001.1110.0010' 0x01E2
482
0x41
On
Underrange
73.1
'0000.0010.1101.1011' 0x02DB
731
73.2
'0000.0010.1101.1100' 0x02DC
732
0x00
Off
Nominal range
1123.2
'0010.1011.1110.0000' 0x2BE0
11232
1123.3
'0010.1011.1110.0001' 0x2BE1
11233
0x42
On
Overrange
1148.2
'0010.1100.1101.1010' 0x2CDA
11482
≥ 1148
.3 '0111.1111.1111.1111' 0x7FFF
32767
0x60
On
Overflow
4.6.1.2 S5-FB250 Format/Kelvin
Table 72: Pt100, Pt200, Pt500, Pt1000 (EN 60751) Setting, S5-FB250 Format/Kelvin
Temperature
[K]
Numeric Value
Status
Byte,
Hex.
Error
LED
Range
Binary
XFÜ
1)
Hex.
Dec.
≤ 47
.0
'1000.0000.0000.0 010'
0x8002
-32766
0x50
On
Underflow
48.0
'0000.0001.1000.0 001'
0x0181
385
0x41
On
Underrange
72.0
'0000.0010.0100.0 001'
0x0241
577
73.0
'0000.0010.0100.1 000'
0x0248
584
0x00
Off
Nominal
range
1123.0
'0010.0011.0001.1 000'
0x2318
8984
1124.0
'0010.0011.0010.0 001'
0x2321
8993
0x42
On
Overrange
1148.0
'0010.0011.1110.0 001'
0x23E1
9185
≥ 1149
.0
'0111.1111.1111.1 010'
0x7FFA
32762
0x60
On
Overflow
1)
Status bits: X= not used, F= error, Ü= overflow