![WAGO 750-489 Manual Download Page 74](http://html1.mh-extra.com/html/wago/750-489/750-489_manual_868450074.webp)
74 Process Image
WAGO-I/O-SYSTEM 750
750-489 4AI RTD/TC/Strain Gauge Ex i
Manual
Version 1.1.0, valid from FW Version 02
4.6.2
Ni100, Ni120, Ni200, Ni500, Ni1000 (TK6180, DIN 43760),
Ni1000 (TK5000, DIN 43760)
4.6.2.1 Standard Format/Kelvin
The possible numeric range corresponds to the temperature range from +213.2 K
to +523.2 K, meaning it ranges from +2132 to +5232.
Table 73: Ni100, Ni120, Ni200, Ni500, Ni1000 Setting – Standard Format/Kelvin
Temperature [K]
Numeric Value
Status
Byte,
Hex.
Error
LED
Range
Binary
Hex.
Dec.
≤
188.1
'1000.0000.0000.0000'
0x8000 -32768
0x50
On
Underflow
188.2
'0000.0111.0101.1010'
0x075A
1882
0x41
On
Underrange
213.1
'0000.1000.0101.0011'
0x0853
2131
213.2
'0000.1000.0101.0100'
0x0854
2132
0x00
Off
Nominal
range
523.2
'0001.0100.0111.0000'
0x1470
5232
523.3
'0001.0100.0111.0001'
0x1471
5233
0x42
On
Overrange
548.2
'0001.0101.0110.1010'
0x156A
5482
≥
548.3
'0111.1111.1111.1111'
0x7FFF 32767
0x60
On
Overflow
4.6.2.2 S5-FB250 Format/Kelvin
Table 74: Ni100, Ni120, Ni200, Ni500, Ni1000 Setting – S5-FB250 Format/Kelvin
Temperature
[K]
Numeric Value
Status
Byte,
Hex.
Error
LED
Range
Binary
XFÜ
1)
Hex.
Dec.
≤ 187
.0
'1000.0000.0000.0 010'
0x8002
-32766
0x50
On
Underflow
188.0
'0000.0101.1110.0 001'
0x05E1
1505
0x41
On
Underrange
212.0
'0000.0110.1010.0 001'
0x06A1
1697
213.0
'0000.0110.1010.1 000'
0x06A8
1704
0x00
Off
Nominal
range
523.0
'0001.0000.0101.1 000'
0x1058
4184
524.0
'0001.0000.0110.0 001'
0x1061
4193
0x42
On
Overrange
548.0
'0001.0001.0010.0 001'
0x1121
4385
≥ 549
.0
'0111.1111.1111.1 010'
0x7FFA
32762
0x60
On
Overflow
1)