WAGO-I/O-SYSTEM 750
Process Image 59
750-489 4AI RTD/TC/Strain Gauge Ex i
Manual
Version 1.1.0, valid from FW Version 02
4.5
Temperature Measurement (Fahrenheit)
For RTD/TC measurements in the
standard format/Fahrenheit
, the temperature
values are represented at a resolution of one digit per 0.1 °F.
In the
S5-FB250 format/Fahrenheit
(RTD/TC measurement with “Fahrenheit”
setting, with S5-FB250 format activated), the temperature values are represented
at a resolution of one digit per 1.0 °F. The status information is represented in bit
0 to bit 2 and the digitized measured value in bit 3 to bit 15.
Representation in the tables: Corresponding monitoring must be switched
on!
The “Underflow”, “Overflow”, “Underrange” and “Overrange” areas require that
the corresponding monitoring is switched on (see Section “Diagnostics” >
“Behavior of the I/O Module in the Event of Error”).