![WAGO 750-489 Manual Download Page 66](http://html1.mh-extra.com/html/wago/750-489/750-489_manual_868450066.webp)
66 Process Image
WAGO-I/O-SYSTEM 750
750-489 4AI RTD/TC/Strain Gauge Ex i
Manual
Version 1.1.0, valid from FW Version 02
4.5.3.9 TC Type K – Standard Format/Fahrenheit
Table 59: TC Type K Setting – Standard Format/Fahrenheit
Temperature
[°F]
Numeric Value
1)
Status
Byte,
Hex.
Error
LED
Range
Binary
Hex.
Dec.
≤
-373.1
'1000.0000.0000.0000'
0x8000 -32768
0x50
On
Underflow
-373.0
'1111.0001.0110.1110'
0xF16E
-3730
0x41
On
Underrange
-328.1
'1111.0011.0010.1111'
0xF32F
-3281
-328.0
'1111.0011.0011.0000'
0xF330
-3280
0x00
Off
Nominal
range
2502.0
'0110.0001.1011.1100'
0x61BC 25020
2502.1
'0110.0001.1011.1101'
0x61BD 25021
0x42
On
Overrange
2547.0
'0110.0011.0111.1110'
0x637E 25470
≥ 2547.1
'0111.1111.1111.1111'
0x7FFF 32767
0x60
On
Overflow
1)
Process values below 0 are represented in binary form as the two’s complement.
4.5.3.10 TC Type K – S5-FB250 Format/Fahrenheit
Table 60: TC Type K Setting – S5-FB250 Format/Fahrenheit
Temperature
[°F]
Numeric Value
Status
Byte,
Hex.
Error
LED
Range
Binary
XFÜ
1)
Hex.
Dec.
≤
-374.0
'1000.0000.0000.0 010'
0x8002
-32766
0x50
On
Underflow
-373.0
'1111.0100.0101.1 001'
0xF459
-2983
0x41
On
Underrange
-329.0
'1111.0101.1011.1 001'
0xF5B9
-2631
-328.0
'1111.0101.1100.0 000'
0xF5C0
-2624
0x00
Off
Nominal
range
2502.0
'0100.1110.0011.0 000'
0x4E30
20016
2503.0
'0100.1110.0011.1 001'
0x4E39
20025
0x42
On
Overrange
2547.0
'0100.1111.1001.1 001'
0x4F99
20377
≥ 2548.0
'0111.1111.1111.1 010'
0x7FFA
32762
0x60
On
Overflow
1)
Status bits: X= not used, F= error, Ü= overflow