ER SERIES ELECTRIC FRYERS - TROUBLESHOOTING
F35613 (
September
2003)
Page 43 of 48
SOLID STATE OR COMPUTER
CONTROL HARNESS PIN-OUTS
PIN NO.
INPUTS
PIN NO.
OUTPUTS
3
C2-1
24VAC Hot
C2-8
24VDC (+) Heat Demand
C2-2
24VAC Neutral
1
C2-9
Not used at this time
2
C2-3
Probe High (red)
C2-10
24VDC (+) Right Basket Lift
C2-4
Probe Low (white)
C2-11
24VDC (+) Left Basket Lift
C2-5
Drain Valve Interlock (24VAC) N.O.
C2-12
No connection
C2-6
Heat Status (24VAC)
---
---
C2-7
Lift Relay DC (-) Common
---
---
NOTES:
1. Connected to ground internally. 2. Available for external buzzer output (24VDC).
3. Outputs to Control Interface Board.
CONTROL INTERFACE BOARD
PIN-OUTS
PIN NO.
INPUTS
PIN NO.
OUTPUTS
P1
24VDC (+) Left Basket Lift
P6
Heat Demand, Triac (24VAC)
2
P2
24VDC (+) Right Basket Lift
P7
System Ground
P3
24VDC (+) Heat Demand Control, Triac
P8
24VAC Right Basket Lift
3
P4
Lift Relay DC (-) Common
P9
24VAC Left Basket Lift
3
P5
Heat Demand, Triac (24VAC)
---
---
P10
Relay Contacts Common (24VAC)
1
---
---
NOTES:
1. Relays connected internally. 2. To R1 heat relay coil.
3. To basket lift relay coil.
FRYMATE (DUMP STATION)
WITH OPTIONAL HEATER
SYMPTOM
POSSIBLE CAUSES
No heat.
1. Unplugged.
2. Power switch off or inoperative.
3. Main circuit breaker off or open.
4. Malfunctioning heat assembly.
Summary of Contents for ERC50
Page 35: ...ER SERIES ELECTRIC FRYERS ELECTRICAL OPERATION F35613 September 2003 Page 35 of 48 ...
Page 37: ...ER SERIES ELECTRIC FRYERS ELECTRICAL OPERATION F35613 September 2003 Page 37 of 48 ...
Page 45: ...ER SERIES ELECTRIC FRYERS TROUBLESHOOTING F35613 September 2003 Page 45 of 48 NOTES ...
Page 46: ...ER SERIES ELECTRIC FRYERS TROUBLESHOOTING F35613 September 2003 Page 46 of 48 NOTES ...
Page 47: ...ER SERIES ELECTRIC FRYERS TROUBLESHOOTING F35613 September 2003 Page 47 of 48 NOTES ...