Thermostat
Communication objects and ETS parameters
Proportional/integral band (A/B)
ETS text
Values available
Comment
[
Default value
]
Integral Cooling
Value
5 min.
To be set according to the
characteristics of the system
and the room (consult a
heating engineer)
6 min.
7 min.
8 min.
9 min.
10 min.
12 min.
15 min.
17 min.
20 min.
25 min.
30 min.
40 min.
50 min.
60 min.
90 min.
120 min.
[20 min.]
Proportional
Heating Value
0 = Off
1.0 °C
1.1 °C
1.2 °C
1.3 °C
1.4 °C
1.5 °C
1.6 °C
1.7 °C
1.8 °C
2.0 °C
2.2 °C
2.5 °C
3.0 °C
3.5 °C
4.0 °C
4.5 °C
5.0 °C
[3.0 °C]
Integral Heating
Value
0=Off
5 min.
6 min.
7 min.
8 min.
9 min.
10 min.
12 min.
15 min.
17 min.
20 min.
25 min.
30 min.
40 min.
50 min.
60 min.
90 min.
120 min.
[20 min.]
Differential
Coefficient
0.1… 1.0 °C
For On/Off type control:
set the thermostat (A/B)
hysteresis that determines
activation/deactivation of
the system with reference to
the difference between the
setpoint and the measured
temperature
[1=0.2]
Continued
Integral band (A/B)