13
No. ETS name
Function
Description
Type
Flag 1
Priority
C R W T U I
108 NOT USED
109 General
Alarm
Used for viewing, on the thermostat display, the trigger-
ing of a generic alarm on the KONNEX BUS
1 bit
C R -
T -
-
Low
110 Input
Input
Device IN control
1 bit
C R -
T -
-
Low
111 Input Status
Input
Device input status. It appears if the input is set as
"general use" and "Toggle rising/falling edge"
1 bit
C -
W -
U -
Low
112 On/Off
Relay
Device relay control (setting relay operating parameters
as "general use")
1 bit
C -
W -
U -
Low
113 Status
Relay
Device relay status (setting relay operating parameters
as "general use")
1 bit
C R -
T -
-
Low
114 Value
Humidity
To know and view the humidity read by a KNX probe
connected to the bus
1 byte
C -
W -
U -
Low
114 Value
Humidity
To know and view the humidity read by a KNX probe
connected to the bus (*)
2 byte
C -
W -
U -
Low
115 Setpoint shift increase Setpoint
To control an increase equivalent to “setpoint shift step”
of the current current setpoint (setpoint set by ETS on
the thermostat for the various operating modes CMF,
STBY, etc.). The temperature shift permitted is limited to
the range set by the parameter: Guest Control Permitted
1 bit
C -
W -
U -
Low
116 Setpoint shift decrease Setpoint
To control a decrease equivalent to “setpoint shift step”
of the current current setpoint (setpoint set by ETS on
the thermostat for the various operating modes CMF,
STBY, etc.). The temperature shift permitted is limited
to the range set by the parameter: Guest Control Per-
mitted.
1 bit
C -
W -
U -
Low
Thermostat
Communication objects and ETS parameters
Number of communication objects
Max. number of group addresses
Max. number of associations
109
254
255
Continued
(*)
This datapoint is only available starting from firmware version 2.00 and later.
COMMUNICA
TION OBJECTS