17
Thermostat
Communication objects and ETS parameters
Internal/External Temperature Sensor (Thermostat-A,
Thermostat-B)
ETS text
Values available
Comment
[
Default value
]
Temperature Offset
-2 °C ... .+2 °C
Calibration of ther-
mostat reading (or of
average of probes)
[0]
Cyclic Send Time
0...30 min.
0=Off.
Activates cyclic
send of object no.
0 "Internal Sensor"
or no. 1 "External
Sensor" (both for the
thermostat A and for
thermostat B)
[0 = Off]
Internal/external temperature sensor
Sensor parameters
ETS text
Values available
Comment
[
Default value
]
Send on Change
0... 1.0 °C
Sets the minimum
measured tem-
perature change
with respect to the
setpoint that will
cause the thermostat
to send the current
value over the bus to
a supervisor.
[0 = Off]
Continued
Continued
Thermostat (A/B)
ETS text
Values available
Comment
[
Default value
]
Guest control per-
mitted
0 = Off
Determine how much the
guest can change the set-
point from the value set on
the thermostat (up/down)
1 = 1.0 °C
2 = 2.0 °C
3 = 3.0 °C
4 = 4.0 °C
5 = 5.0 °C
6 = No Limitation
[3]
Thermostat (A/B)
Guest control permitted
Current Temperature (A/B)
ETS text
Values available
Comment
[
Default value
]
Temperature sen-
sor weightings
0... 100
For the thermostat's internal
sensor, the Vimar wired NTC
probe (if present) and the KNX
probes, this determines the
relative importance for calcu-
lating the weighted average
of the measured temperatures
[0]
Cyclic Send Time
0 = Off
Sets the frequency in
minutes with which the ther-
mostat (A/B) must send the
measured temperature value
(or the weighted average of
the probes) over the bus to
a supervisor. Activates cyclic
send of object no. 10 and
11 "Current Temperature" of
thermostat A/B
11 = 30 min.
[0 = Off]
Send on Change
0 = Off
Sets the temperature difference
measured by the thermostat
(A/B) that results in the read val-
ue (or the weighted average of
the probes) being sent over the
bus towards a supervisor. Acti-
vates cyclic send of object no.
10 and 11 "Current Tempera-
ture" of thermostat A/B
1.0 = 1.0 °C
[0 = Off]
Current temperature (A/B)
Note:
If you use the Well Contact Suite supervision system to
update the value displayed by the supervision station of the “A/B
Current Temperature" linked to objects nos. 10 and 11, you
must enable cyclic send or send on change. In the event of a
conjunction of a high number of thermostats, it is not advisable
to enable numerous cyclic sends with timing that is too low to
avoid overloading the BUS communications.
COMMUNICA
TION OBJECTS
ETS text
Values available
Comment
[
Default value
]
Setpoint shift step
0.1, 0.2....1
For thermostat A setpoint
shift step upon receipt of
control on objects 115 and
116
[1]