12
Thermostat
Communication objects and ETS parameters
No. ETS name
Function
Description
Type
Flag 1
Priority
C R W T U I
88
V2 speed
B: Fan Inputs
Used to force activation of fan coil speed V2 (if the
selected fan has 3 speeds)
1 bit
C
- W - U - Low
89
V3 speed
B: Fan Inputs
Used to force activation of fan coil speed V3 (if the
selected fan has 3 speeds)
1 bit
C
- W - U - Low
90
Automatic
B: Fan Inputs
Used to force activation of fan coil speed AUTO (if the
selected fan has 3 speeds)
1 bit
C
- W - U - Low
91
Proportional (0- 100%) B: Fan Outputs
Used to read the proportional speed of the fan coil fan (if
the selected fan is proportional or 8-bit with 3 speeds).
This object is used for controlling proportional actuators.
1 byte
C R - T - - Low
92
Off
B: Fan Outputs
Used to read the deactivation status of all 3 speeds (if
the selected fan has 3 speeds). The thermostat sends a
1 bit when the fan is off (fan coil speed 0).
1 bit
C R - T -
- Low
93
V1 speed
B: Fan Outputs
This is the object to pair with the relay of speed 1 of the
fan coil (to read the status of speed V1 of the fan coil,
this object can be polled by the bus)
1 bit
C R - T - - Low
94
V2 speed
B: Fan Outputs
This is the object to pair with the relay of speed 2 of the
fan coil (to read the status of speed V2 of the fan coil,
this object can be polled by the bus)
1 bit
C R - T -
- Low
95
V3 speed
B: Fan Outputs
This is the object to pair with the relay of speed 3 of the
fan coil (to read the status of speed V3 of the fan coil,
this object can be polled by the bus)
1 bit
C R - T - - Low
96
V1 speed
B: Fan Disable
To disable speed V1 (if the selected fan has 3 speeds)
1 bit
C R W T U - Low
97
V2 speed
B: Fan Disable
To disable speed V2 (if the selected fan has 3 speeds)
1 bit
C R W T U - Low
98
V3 speed
B: Fan Disable
To disable speed V3 (if the selected fan has 3 speeds)
1 bit
C R W T U - Low
Thermostat B: window
99
Window Sensor
B: Window
Object to be paired with the input to which a win-
dow-contact is connected so that the thermostat
switches to OFF-PROTECTED when the window is
opened, depending on whether the mode is Air Condi-
tioning or Heating
1 bit
C
- W - U - Low
Thermostat B: scenario
100 Scenario
B: Scenario
To activate a scenario with a 1 Byte message
1 byte
C
- W - U - Low
Thermostat B: Auto/Man
101 Temperature: Automat-
ic/Manual
B: Manual operation
To see whether the guest has altered the thermostat
temperature setpoint with respect to the default setting 1 bit
C R - T - - Low
102 Fan coil: Automatic/
Manual
B: Manual operation
To see whether the guest has altered the fan coil speed
with respect to the default setting
1 bit
C R - T - - Low
103 Temperature: Disable
Local operation
B: Manual operation
Activating this object prevents the guest from altering
the setpoint temperature by means of the thermostat
buttons with respect to the value set by the bus
1 bit
C
- W - U - Low
104 Fan coil: Disable Local
Operation
B: Manual operation
Activating this object prevents the guest from altering
the fan coil speed by means of the thermostat buttons
with respect to the value set by the bus
1 bit
C
- W - U - Low
Thermostat B: Floor Probe Alarm
105 Floor Temperature
B: Alarm
If the temperature limitation is active an alarm is sent
when the temperature exceeds the set threshold
1 bit
C R -
T -
-
Low
GLOBAL
106 Initialisation
Alarm
Do not use
: it is used for automatic testing during
production of the device
1 bit
C R - T -
- Low
107 NOT USED
Continued
Continued
C
= Communication;
R
= Read;
W
= Write;
T
= Transmission;
U
= Enable update