9
No. ETS name
Function
Description
Type
Flag 1
Priority
C R W T U I
35
Heating Valve
A: Valve
If the "Valve" parameter is set for 4-pipe proportional
systems for Winter valve management: to be used to
control the head of a radiating system or for the propor-
tional valve of a fan coil
1 byte
C R - T - - Low
Thermostat A: Second Stage
36
Cooling Valve
A: 2
nd
Cooling Stage
If second cooling stage is enabled to be used for the
boost function (cooling) for on/off valve control
1 bit
C R - T -
- Low
36
Cooling Valve
A: 2
nd
Cooling Stage
If second cooling stage is enabled to be used for the
boost function (cooling) for proportional valve control
1 byte
C R - T -
- Low
37
Heating Valve
A: 2
nd
Heating Stage
If second heating stage is enabled to be used for the
boost function (heating) for on/off valve control
1 bit
C R - T -
- Low
37
Heating Valve
A: 2
nd
Heating Stage
If second heating stage is enabled to be used for the
boost function (heating) for proportional valve control
1 byte
C R - T -
- Low
Thermostat A: Fan
38
Proportional (0- 100%) A: Fan Inputs
Used to set a proportional speed for the fan coil fan (if
the selected fan is proportional with 3 speeds) via a su-
pervisor (e.g., touch screen)
1 byte
C
- W - U - Low
39
NOT USED
40
V1 speed
A: Fan Inputs
Used to force activation of fan coil speed V1 (if the
selected fan has 3 speeds)
1 bit
C
- W - U - Low
41
V2 speed
A: Fan Inputs
Used to force activation of fan coil speed V2 (if the
selected fan has 3 speeds)
1 bit
C
- W - U - Low
42
V3 speed
A: Fan Inputs
Used to force activation of fan coil speed V3 (if the
selected fan has 3 speeds)
1 bit
C
- W - U - Low
43
Automatic
A: Fan Inputs
Used to force activation of fan coil speed AUTO (if the
selected fan has 3 speeds)
1 bit
C
- W - U - Low
44
Proportional (0- 100%) A: Fan Outputs
Used to read the proportional speed of the fan coil fan
(if the selected fan is proportional with 3 speeds with the
8-Bit Object - Proportional (0-100%). This object is used
for controlling proportional actuators.
1 byte
C R - T - - Low
45
Off
A: Fan Outputs
Used to read the deactivation status of all 3 speeds (if
the selected fan has 3 speeds). The thermostat sends a
1 bit when the fan is off (fan coil speed 0).
1 bit
C R - T -
- Low
46
V1 speed
A: Fan Outputs
This is the object to pair with the relay of speed 1 of the
fan coil (to read the status of speed V1 of the fan coil,
this object can be polled by the bus)
1 bit
C R - T - - Low
47
V2 speed
A: Fan Outputs
This is the object to pair with the relay of speed 2 of the
fan coil (to read the status of speed V2 of the fan coil,
this object can be polled by the bus)
1 bit
C R - T -
- Low
48
V3 speed
A: Fan Outputs
This is the object to pair with the relay of speed 3 of the
fan coil (to read the status of speed V3 of the fan coil,
this object can be polled by the bus)
1 bit
C R - T - - Low
49
V1 speed
A: Fan Disable
To disable speed V1 (if the selected fan has 3 speeds)
1 bit
C R W T U - Low
50
V2 speed
A: Fan Disable
To disable speed V2 (if the selected fan has 3 speeds)
1 bit
C R W T U - Low
51
V3 speed
A: Fan Disable
To disable speed V3 (if the selected fan has 3 speeds)
1 bit
C R W T U - Low
Thermostat A: Window
52
Window Sensor
A: Window
Object to be paired with the input to which a win-
dow-contact is connected so that the thermostat
switches to OFF-PROTECTED when the window is
opened, depending on whether the mode is Air Condi-
tioning or Heating
1 bit
C
- W - U - Low
Thermostat
Continued
C
= Communication;
R
= Read;
W
= Write;
T
= Transmission;
U
= Enable update
Continued
Communication objects and ETS parameters
COMMUNICA
TION OBJECTS