11
No. ETS name
Function
Description
Type
Flag 1
Priority
C R W T U I
72
Winter Comfort
B: Setpoint - status, control
To read and set the Winter Comfort setpoint.
2 byte
C R W T U
- Low
73
Winter Standby
B: Setpoint - status, control
To read and set the Winter Standby setpoint
2 byte
C R W T U
- Low
74
Winter Energy Saving
B: Setpoint - status, control
To read and set the Winter Economy setpoint
2 byte
C R W T U
- Low
75
Winter Protected
B: Setpoint - status, control
To read and set the Winter Antifreeze setpoint
2 byte
C R W T U
- Low
76
Summer Comfort
B: Setpoint - status, control
To read and set the Summer Comfort setpoint
2 byte
C R W T U
- Low
77
Summer Standby
B: Setpoint - status, control
To read and set the Summer Standby setpoint
2 byte
C R W T U
- Low
78
Summer Energy Saving B: Setpoint - status, control
To read and set the Summer Economy setpoint
2 byte
C R W T U
- Low
79
Summer Protected
B: Setpoint - status, control
To read and set the Summer Too Hot setpoint (power-off
of climate control if the window is opened, for instance) 2 byte
C R W T U
- Low
80
NOT USED
Thermostat B: Valves
81
Cooling/Heating Valve
B: Valve
If the "Valve" parameter is set for 2-pipe systems for
valve management: to be used to control the head of a
radiating system or the On/Off valve of a fan coil
1 bit
C R - T - - Low
81
Cooling Valve
B: Valve
If the "Valve" parameter is set for 4-pipe systems for
valve management in Summer: to be used to control
the head of a radiating system or the On/Off valve of a
fan coil
1 bit
C R - T - - Low
82
Heating Valve
B: Valve
If the "Valve" parameter is set for 4-pipe systems for
valve management in Winter: to be used to control the
head of a radiating system or the On/Off valve of a fan
coil
1 bit
C R - T - - Low
81
Cooling/Heating Valve
B: Valve
If the "Valve" parameter is set for 2-pipe proportional
systems for proportional valve management: to be
used to control the head of a radiating system or for the
proportional valve of a fan coil
1 byte
C R - T - - Low
81
Cooling Valve
B: Valve
If the "Valve" parameter is set for 4-pipe proportional
systems for Summer valve management: to be used to
control the head of a radiating system or for the propor-
tional valve of a fan coil
1 byte
C R - T - - Low
82
Heating Valve
B: Valve
If the "Valve" parameter is set for 4-pipe proportional
systems for Winter valve management: to be used to
control the head of a radiating system or for the propor-
tional valve of a fan coil
1 byte
C R - T - - Low
Thermostat B: Second Stage
83
Cooling Valve
B: 2
nd
Cooling Stage
If second cooling stage is enabled to be used for the
boost function (cooling) for on/off valve control
1 bit
C R - T -
- Low
83
Cooling Valve
B: 2
nd
Cooling Stage
If second cooling stage is enabled to be used for the
boost function (cooling) for proportional valve control
1 byte
C R - T -
- Low
84
Heating Valve
B: 2
nd
Heating Stage
If second heating stage is enabled to be used for the
boost function (heating) for on/off valve control
1 bit
C R - T -
- Low
84
Heating Valve
B: 2
nd
Heating Stage
If second heating stage is enabled to be used for the
boost function (heating) for proportional valve control
1 byte
C R - T -
- Low
Thermostat B: Fan
85
Proportional (0- 100%) B: Fan Inputs
Used to set a proportional speed for the fan coil fan (if
the selected fan is proportional or 8-bit with 3 speeds)
via a supervisor (e.g., touch screen)
1 byte
C
- W - U - Low
86
NOT USED
87
V1 speed
B: Fan Inputs
Used to force activation of fan coil speed V1 (if the
selected fan has 3 speeds)
1 bit
C
- W - U - Low
Continued
Thermostat
Communication objects and ETS parameters
Continued
C
= Communication;
R
= Read;
W
= Write;
T
= Transmission;
U
= Enable update